INSP-Final Inspection | 3/9/2018 | 3/14/2018 | 3/14/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Peter Phone #: ###-####
|
INSP-Final Inspection | 11/2/2017 | 11/9/2017 | 11/9/2017 | A | CANC |
Troy Cobbley
|
|
|
Cancel per the tech that was on site.
Natalie Phone #: ###-####
|
INSP-Final Inspection | 10/18/2017 | 10/19/2017 | 10/19/2017 | P | FAIL |
Troy Cobbley
|
|
|
Provide 24 hour back up power as per the review comments for the internet form of communication, relocate the smoke detector to be above the facp, provide the shield wire between the AES and facp, remove the horn/strobe from the lobby, provide as-builts showing the two low air and to water flow switches, provide functional testing of the two low air and two water flow switches, provide document box, provide updated map
Peter - new fire alarm panel Phone #: ###-####
|
Issue and Print Permit | | | 10/17/2017 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 9/25/2017 | | 9/25/2017 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/25/2017 | | PASS |
|
|
|
|
Alarm Plan Check | 9/25/2017 | | 9/25/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/25/2017 | | DONE |
|
|
|
Plans approved with review comments and specific requirements.
|
Permit Ready to Issue | | | 9/25/2017 | | DONE |
|
|
|
|
Application received | | | 9/21/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 21 2017 8:21AM
|