INSP-Final Inspection | 5/30/2018 | 5/31/2018 | 5/31/2018 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
Phone #: ###-#### Inspection requested via web by Nathan Price
|
INSP-Alarm Testing | 5/14/2018 | 5/14/2018 | 5/14/2018 | A | PART |
Jim Page
|
|
|
Fire alarm testing for all fire sprinkler related components complete. Audio visual devices on levels 2 through 5 that were obstructed have been moved. Fire alarm testing for levels 2 through 5 complete.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Alarm Testing | 5/11/2018 | 5/11/2018 | 5/11/2018 | A | DONE |
Jim Page
|
|
|
Fire alarm testing for elevator recall and shunt complete.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Alarm Testing | 5/8/2018 | 5/9/2018 | 5/9/2018 | P | PART |
Jim Page
|
|
|
Fire alarm testing complete for levels 2 through 5 (1 through 4 to match designation of floor labeling). Audio visual device needs to be placed on level 5 balconey, audio visual devices blocked by exit signs will need to be relocated to see the effect of the strobe. Relocation of blocked audio visual devices will be verified during fire sprinkler inspection.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
Issue and Print Permit | | | 10/16/2017 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/12/2017 | | DONE |
|
|
|
|
Alarm Plan Check | 10/12/2017 | | 10/12/2017 | | FAIL |
Lee G Meredith
|
|
|
|
Plan resubmittals received | | | 10/12/2017 | | DONE |
|
|
|
|
Alarm Plan Check | 10/12/2017 | | 10/12/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/12/2017 | | DONE |
|
|
|
3rd review plans approved with review comments.
|
Permit Ready to Issue | | | 10/12/2017 | | DONE |
|
|
|
all met
|
Plan assigned to (Lee) | 10/6/2017 | | 10/6/2017 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 10/6/2017 | | FAIL |
|
|
|
See first review comments.
|
Application received | | | 10/3/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 3 2017 3:02PM
|