Permit Information
Permit NumberFIR17-00626
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 2855 W LOCKHEED LN
Project NameBOI ARFF REMODEL/EXPANSION
Customer Number 
ePlanReviewYes
Description
BOI ARFF Remodel/Expansion scope of work is to provide owner required notification, sprinkler monitoring and connection to the existing Main Airport FACP. This work is associated with building permit BLD17-00386.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/5/201912/5/201912/5/2019PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection10/17/201910/18/201910/18/2019APART
DetailsTroy Cobbley
Fire alarm work complete for phase 4. See the city approved plans for the clouded area in red for the specific devices witnessed.

Brian Phone #: ###-####
INSP-Final Inspection10/14/201910/15/201910/15/2019APART
DetailsTroy Cobbley
Phase 4 fire alarm complete. See the city approved plans for the area clouded in red that was inspected for phase 4.
Brian Phone #: ###-####
INSP-Final Inspection10/9/201910/10/201910/10/2019AFAIL
DetailsTroy Cobbley
Placement and function tested. for phase 4 but tech could not provide verification for the candella settings for the strobes in the scope of work. Brian Phone #: ###-####
INSP-Final Inspection10/8/201910/9/201910/9/2019AFAIL
DetailsTroy Cobbley
On site fire man asked us to reschedule since they are using the phase 4 area. Brian Phone #: ###-####
INSP-Alarm Testing2/15/20192/15/20192/15/2019PPART
DetailsJim Page
Fire alarm testing for phase 3 complete, LF sound bases in rooms were a steady tone when alarms are active, LF bases need to be temporal 3 with the rest of the system, temporal sound fo LF bases will need to be verified at final inspection.

After 1PM if possible. Phone #: ###-#### Inspection requested via web by Gary Gambino
INSP-Final Inspection2/4/20192/4/20192/4/2019PPART
DetailsTroy Cobbley
Todays inspection was to verify that the fiber optic interconnection is functional which it was.

ARFF added to all devices descriptions going to the main panel. Phone #: ###-#### Inspection requested via web by Gary Gambino
INSP-Alarm Testing1/30/20192/1/20192/1/2019AFAIL
DetailsTroy Cobbley
The signals did go to the airport control as device and room number but the airport did not have an actual description of the location on site for the alarm. Gary is going to add description and reschedule.

Re-inspect after placing ARFF building on airport network - verification testing that new building reports to the Airport operations center. Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Final Inspection10/25/201810/26/201810/26/2018APART
DetailsTroy Cobbley
Phase 2 work is complete, cellular dialer is being used temporary for 90 days

Phone #: ###-#### Inspection requested via web by Gary Gambino
INSP-Final Inspection10/24/201810/25/201810/25/2018PCANC
DetailsTroy Cobbley
Please call ahead Phone #: ###-#### >> Inspection requested via web by Gary Gambino Inspection cancelled from web by: Gary Gambino
INSP-Final Inspection10/24/201810/24/201810/24/2018PCANC
DetailsTroy Cobbley
Please call ahead Phone #: ###-#### >> Inspection requested via web by Gary Gambino Inspection cancelled from web by: Gary Gambino
Meeting  10/24/2018 DONE
Discussed with Ron Johnson JCI's temporary interface to new fire alarm panel via new fiber optic line. If they are unable to provide this, Ron has allowed them to provide a temporary cellular communicator until the fiber connection is ready. He informed them that they will not be required to get an additional permit to provide the temporary cellular communicator.
INSP-Final Inspection10/17/201810/18/201810/18/2018AFAIL
DetailsTroy Cobbley
Need to pretest interconnection with the fire sprinkler devices, one 15cd strobe is mounted too high, another 15cd strobe is overspaced, missing two weather proof back boxes, drawings show networking with the airport fire alarm system but networking has not been set up so there is no off site or on site communiction. No actual testing performed.


Please call to schedule exact time. Phone #: ###-#### Inspection requested via web by Gary Gambino
Plan resubmittals received  7/25/2018 DONE
Resubmittal includes modifications to the floor plan.
Alarm Plan Check7/25/2018 7/25/2018 PASS
DetailsLee G Meredith
Plans approved as noted on drawings.
PLANS TAKEN FRONT DESK ALARM  7/25/2018 DONE
Plans approved as noted, with review comments.
Override - Parcel Holds  7/25/2018  
Permit Ready to Issue  7/25/2018 DONE
Override - Parcel Holds  7/25/2018  
Issue and Print Permit  7/25/2018 DONE
1st review completed  10/25/2017 FAIL
Notification inadequate in several areas. Documentation of engineer of record approval not provided. Returned to applicant for corrections.
Application received  10/24/2017 DONE
Application submitted via PDS Online on Oct 24 2017 11:47AM
Plan assigned to (Lee)10/24/2017 10/24/2017 DONE
DetailsLee G Meredith