Permit Information
Permit NumberFIR17-00668
StatusFinaled
Name CRANE ALARM SERVICE
Site Address 8013 W FAIRVIEW AVE
Project NameShopko Plaza
Customer Number 
ePlanReviewYes
Description
FACP replacement. replace all existing initiating devices for compatibility, remove all manual pull stations due to FACP replacement, (not required if fully sprinklered). Existing notification, not included in permit set, but will provide plan modification if necessary to relocate.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/20/20189/21/20189/21/2018APASS
DetailsLee G Meredith
Gerry from Colliers is verifying that we will have access to tenant spaces, for example the daycare, H&R Block, and ice cream shop. Meet with Peter from Crane Alarm. Please call the office at ###-#### prior to inspection with a firm time. Thank you. Phone #: ###-#### >> Inspection requested via web by Laura Tyson
DOC - Permit Finaled  9/21/2018 DONE
Duct detection / shutdown and notification tested and approved.
Plan Modification Accepted  4/19/2018 DONE
Existing notification in Kim's Daycare is now being shown.
Alarm Plan Check4/19/2018 4/19/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/19/2018 DONE
Plan mod approved with additional review comments.
Permit Ready to Issue  4/19/2018 DONE
Plan Mod Approved
DO NOT REISSUE
CHANGE STATUS TO (ISS)  4/19/2018 DONE
(F) Reprint permit  4/19/2018 DONE
Miscellaneous action  4/11/2018 DONE
Due to notification changes, Mary requested the work flow be reopened so a plan modification can be uploaded.
INSP-Final Inspection4/4/20184/6/20184/6/2018AFAIL
DetailsTroy Cobbley
The head end equipment was tested. Netcon was a 5. Batteries match and a dedicated circuit has been provied. No sprinkler devices have been tested due to the sprinkler contractor not showing up. We tested duct smoke detectors in multiple tenant spaces and I noted in one space the duct smoke detector did not shut down immediatley as required. Also plan modifications are needed to show the notification devices in the two riser rooms and through out the day care. The ground wire for the AES has not been installed either.

Laura -call for access--owner and Jim from American Fire, and keith, colliers, peter from crane alarm Phone #: ###-####
Miscellaneous action  4/5/2018 DONE
As built drawings emailed by Mary. I responded to let her know that too many changes had taken place and a plan mod will be required.
Alarm Plan Check4/5/2018 4/5/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/5/2018 DONE
Plan mod approved. No additional review comments.
Permit Ready to Issue  4/5/2018 DONE
Plan Mod Approved
DO NOT REISSUE
Issue and Print Permit  4/5/2018 DONE
Plan assigned to (Lee)11/14/2017 11/14/2017 DONE
DetailsLee G Meredith
1st review completed  11/14/2017 FAIL
Failed prescreen review. Audible and visible notification is not shown. Needs to be shown to evaluate visible notification coverage due to fire alarm system replacement requirements.
Alarm Plan Check11/14/2017 11/14/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/14/2017 DONE
Plans approved with review comments.
Permit Ready to Issue  11/14/2017 DONE
Issue and Print Permit  11/14/2017 DONE
Application received  11/13/2017 DONE
Application submitted via PDS Online on Nov 13 2017 2:24PM