INSP-Final Inspection | 9/20/2018 | 9/21/2018 | 9/21/2018 | A | PASS |
Lee G Meredith
|
|
|
Gerry from Colliers is verifying that we will have access to tenant spaces, for example the daycare, H&R Block, and ice cream shop. Meet with Peter from Crane Alarm. Please call the office at ###-#### prior to inspection with a firm time. Thank you. Phone #: ###-#### >> Inspection requested via web by Laura Tyson
|
DOC - Permit Finaled | | | 9/21/2018 | | DONE |
|
|
|
Duct detection / shutdown and notification tested and approved.
|
Plan Modification Accepted | | | 4/19/2018 | | DONE |
|
|
|
Existing notification in Kim's Daycare is now being shown.
|
Alarm Plan Check | 4/19/2018 | | 4/19/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/19/2018 | | DONE |
|
|
|
Plan mod approved with additional review comments.
|
Permit Ready to Issue | | | 4/19/2018 | | DONE |
|
|
|
Plan Mod Approved
DO NOT REISSUE
|
CHANGE STATUS TO (ISS) | | | 4/19/2018 | | DONE |
|
|
|
|
(F) Reprint permit | | | 4/19/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 4/11/2018 | | DONE |
|
|
|
Due to notification changes, Mary requested the work flow be reopened so a plan modification can be uploaded.
|
INSP-Final Inspection | 4/4/2018 | 4/6/2018 | 4/6/2018 | A | FAIL |
Troy Cobbley
|
|
|
The head end equipment was tested. Netcon was a 5. Batteries match and a dedicated circuit has been provied. No sprinkler devices have been tested due to the sprinkler contractor not showing up. We tested duct smoke detectors in multiple tenant spaces and I noted in one space the duct smoke detector did not shut down immediatley as required. Also plan modifications are needed to show the notification devices in the two riser rooms and through out the day care. The ground wire for the AES has not been installed either.
Laura -call for access--owner and Jim from American Fire, and keith, colliers, peter from crane alarm Phone #: ###-####
|
Miscellaneous action | | | 4/5/2018 | | DONE |
|
|
|
As built drawings emailed by Mary. I responded to let her know that too many changes had taken place and a plan mod will be required.
|
Alarm Plan Check | 4/5/2018 | | 4/5/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/5/2018 | | DONE |
|
|
|
Plan mod approved. No additional review comments.
|
Permit Ready to Issue | | | 4/5/2018 | | DONE |
|
|
|
Plan Mod Approved
DO NOT REISSUE
|
Issue and Print Permit | | | 4/5/2018 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 11/14/2017 | | 11/14/2017 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/14/2017 | | FAIL |
|
|
|
Failed prescreen review. Audible and visible notification is not shown. Needs to be shown to evaluate visible notification coverage due to fire alarm system replacement requirements.
|
Alarm Plan Check | 11/14/2017 | | 11/14/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/14/2017 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 11/14/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/14/2017 | | DONE |
|
|
|
|
Application received | | | 11/13/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 13 2017 2:24PM
|