Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR17-00670
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 877 N LIBERTY ST
Project NameADA COUNTY PARAMEDIC STATION 2
Customer Number 
ePlanReviewYes
Description
[ADA County Station 21]
The fire sprinkler scope of work consists of installing one new wet system with 68 sprinklers in this new 3,794 ft² building. The building is constructed of both combustible and non-combustible materials. The wood attic space above the rooms and offices shall have CCS sprinklers, draft stopped to 1000 ft² sections or less. All sprinkler will be quick response type. The 6" C-900 underground will supply a 4" backflow and 4" main with 1¼" branch lines. The FDC and bell will be on the front of the building face the street.

• The underground piping is under permit FIR17-00632.

[BLD17-02384]
One story 3794 sf paramedic station with 3-vehicle garage, day room, kitchen, offices, bedrooms, exterior covered porch with perimeter seating wall. One driveway to east for (2) ambulance bays, one driveway to north for (1) battalion chief vehicle. Facility replaces existing building north of new building; staff parking will remain in St. Alphonsus lot (no parking on site). Site is fully landscaped with subsurface drainage. Grease interceptor in ambulance driveway.

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There is one AMM at this time. The AMM does not pertain to the fire protection.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/17/20184/18/20184/18/2018PPASS
DetailsTroy Cobbley
Permit finaled
Plan Modification Accepted  4/17/2018 DONE
Sprinkler Plan Check4/17/2018 4/17/2018 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  4/17/2018 DONE
Issue and Print Permit  4/17/2018 DONE
INSP-Final Inspection4/11/20184/12/20184/12/2018AFAIL
DetailsTroy Cobbley
Provide clearance around the underground supply. It appears the backflow preventor is causing the flow switch to "cycle". This issue needs resolve. The forward flush passed but if the backflow assembly is changed it will need redone. Plans may need to be resubmitted if changes are made.

George Jess is the contact for this inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection4/10/20184/11/20184/11/2018PCANC
DetailsTroy Cobbley
George Jess is the contact for this inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
Plan Modification Accepted  4/10/2018 DONE
Sprinkler Plan Check4/10/2018 4/10/2018 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  4/10/2018 DONE
(F) Reprint permit  4/10/2018 DONE
Permit Ready to Issue  4/10/2018 DONE
CHANGE STATUS TO (ISS)  4/10/2018 DONE
INSP-Sprinkler Rough-in3/23/20183/26/20183/26/2018APASS
DetailsTroy Cobbley
Coreections have been made. Piping can be covered


George Jess is the contact for this rough to cover inspection. Thanks for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in3/19/20183/20/20183/20/2018APART
DetailsTroy Cobbley
Provide flexible couplings on both sides of the CMU wall, provide sprinkler protection in small room as discussed, provide branchline restraints as shown on the plans, provide verification that the CC heads are listed for 9' off of walls. Provide all of the missing small documents

George Jess is the contact for this inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro2/15/20182/16/20182/16/2018APASS
DetailsTroy Cobbley
Overhead hydro test passed
INSP-Sprinkler Rough-in/Hydro2/14/20182/15/20182/15/2018PCANC
DetailsTroy Cobbley
I'm unable to make it back for this hydro test. To be rescheduled for tomorrow


George Jess is the contact for this overhead hydro. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in1/31/20181/31/20181/31/2018PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, hardlids approved for cover.
INSP-Sprinkler Rough-in1/29/20181/29/20181/29/2018PCANC
DetailsTroy Cobbley
To be re-scheduled per George.

George Jess is the contact for this rough in inspection. He is hoping for an appointment in the pm. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in11/29/201711/30/201711/29/2017ACANC
DetailsTroy Cobbley
Bryan Collins is the contact for this Underground Rough-in. Thank you for your time. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
Issue and Print Permit  11/29/2017 DONE
Sprinkler Plan Check11/22/2017 11/22/2017 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  11/22/2017 DONE
DetailsTim Frost
Permit Ready to Issue  11/22/2017 DONE
Intake Approval  11/20/2017 PASS
Plan assigned to (Tim)11/20/2017 11/20/2017 DONE
DetailsTim Frost
Application received  11/14/2017 DONE
Application submitted via PDS Online on Nov 14 2017 8:15AM