INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in | 1/19/2018 | 1/22/2018 | 1/22/2018 | P | PEND |
Scott Arellano
|
|
|
Inspection completed with the exception of 3 finish escutcheons in new rooms and upright shell protection masked off due to painting. Final approval will be subject to completion of associated building shell fire alarm permit (FIR17-00630).
|
INSP-Sprinkler Rough-in | 1/19/2018 | 1/19/2018 | 1/19/2018 | P | CANC |
Troy Cobbley
|
|
|
Contact Scott Powada - ###-#### 30 min prior to RTC Insp start.
Please Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
Sprinkler Plan Check | 1/18/2018 | | 1/18/2018 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/18/2018 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 1/18/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/18/2018 | | DONE |
|
|
|
|
(F) Reprint permit | | | 1/18/2018 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/10/2018 | | 1/10/2018 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 1/10/2018 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Sprinkler Plan Check | 1/3/2018 | | 1/3/2018 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 1/3/2018 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Plan resubmittals received | | | 1/3/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/3/2018 | | FAIL |
|
|
|
Did not add a new review. The previous comments were not corrected. I sent an email to Phoenix Fire Protection and ask them to make ALL of the changes and then I would look at it again.
|
Intake Approval | | | 11/27/2017 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 11/27/2017 | | 11/27/2017 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/27/2017 | | 11/27/2017 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 11/27/2017 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 11/27/2017 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 11/21/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 21 2017 12:55PM
|