Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR17-00690
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7590 W VICTORY RD
Project NameCURTIS RESTAURANT EQUIPMENT
Customer Number 
ePlanReviewYes
Description
[Curtis Restaurant Equipment]
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration. The ESFR sprinklers are being changed to extra-large orifice k=11.2 sprinklers. New calculations were provided.

Location on Plan - Warehouse
Commodity - Stainless Steel Commercial Cooking Equipment
Classification - Class I
Storage Type (rack, solid pile, etc.) - Rack
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 14’
Ceiling Height - 22’
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - k=11.2, 212º, R3216
High Temperature Sprinklers Required - No
Applicable NFPA Section - 16.2.1.3.2(a), .33/2000, 16.2.1.3.4.1, 60%
Hydraulic Design Criterion - .198/2000
Hose Stream Requirements - 500

Location on Plan - Showroom
Commodity - Commercial Cooking Equipment in Boxes
Classification - Group A
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - 8
Height of Storage - 15’
Ceiling Height - 22’
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - K=11.2, 212º
High Temperature Sprinklers Required - No
Applicable NFPA Section - 17.2.1.2.1(b) Footnote 2
Hydraulic Design Criterion - .45/2000
Hose Stream Requirements - 500

[BLD17-02486]
The fire sprinkler system is used for building area increase and for fire area. To create a 12,181 square foot sales and warehouse tenant space within a new 21,885 square foot building. The building shell was constructed under permit BLD17-00763. Work is to include a tenant demising wall, interior nonbearing walls, two toilet rooms accessible to the disabled, a new double leaf exterior door, exterior wall infills, suspended acoustical ceilings, gypsum board ceilings, millwork, and finishes. A separate racking permit is required for racks more than 8 feet tall. The future test kitchen will be done under a separate permit. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**

Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  4/18/2018 DONE
DetailsChristina Prado
Incorrect address assigned throughout review and completion. Correct address is 7590 W Victory Rd., not listed 7552 W Victory. All project addresses updated 4/18/18 by C_P and new CO issued
INSP-Final Inspection12/4/201712/6/201712/6/2017APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/4/201712/6/201712/4/2017PCANC
DetailsTroy Cobbley
We would like to coo shell permit final also. Please call Kerry Turner with time frame. Phone #: ###-#### >> Inspection requested via web by Jeff Packham Inspection cancelled from web by: Jeff Packham
INSP-Conference12/1/201712/1/201712/1/2017ADONE
DetailsTroy Cobbley
Jeff and I spoke about the conditions for final sign offs for the shell and TI permits.
INSP-Sprinkler Rough-in12/1/201712/1/201712/1/2017APASS
DetailsTroy Cobbley
Piping above the ceilings is ok for cover. Also Need all typical items for final, signs/stickers..ect and also need the pipe sizing to the heads under hvac units and doors addressed and heads changed out at the unit heaters.


wrong cell phone input my apologies. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Sprinkler Rough-in11/30/201712/1/201712/1/2017AFAIL
DetailsTroy Cobbley
I left two voice messages for contact. I went to project site and made no contact. No inspection performed.

Please call Jeff when available. I will meet you first thing am. Thank you. Phone #: ###-#### Inspection requested via web by Jeff Packham
Issue and Print Permit  11/30/2017 DONE
(F) Reprint permit  11/30/2017 DONE
Intake Approval  11/29/2017 PASS
Plan assigned to (Tim)11/29/2017 11/29/2017 DONE
DetailsTim Frost
Sprinkler Plan Check11/29/2017 11/29/2017 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  11/29/2017 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  11/29/2017 DONE
DetailsTim Frost
Permit Ready to Issue  11/29/2017 DONE
Application received  11/22/2017 DONE
Application submitted via PDS Online on Nov 22 2017 12:28PM