Permit NumberFIR17-00693
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY
Site Address 7709 W OVERLAND RD Unit: 120
Project NameMad Mac - Occupancy
Customer Number 
ePlanReviewNo
Description
**modified scope for new ansul r-102 for existing range hood 12/4/17** retro fit existing Amerex KP wet chemical restaurant fire system to protect new appliance line up
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/8/201712/8/201712/8/2017PPASS
DetailsTroy Cobbley
Permit finaled. Hood suppression system functioned correctly.

Nate Phone #: ###-####
(F) Reprint permit  12/4/2017 DONE
INSP-Final Inspection11/29/201711/30/201711/30/2017PFAIL
DetailsTroy Cobbley
No plans or small documents on site, Manual pull is too close to hood and mounted too high, suppression system did not discharge when test link was cut.

Nate Phone #: ###-####
Application received  11/27/2017  
Permit Ready to Issue  11/27/2017 DONE
Issue and Print Permit  11/27/2017 DONE