Information based on query as of Saturday, September 19, 2026.
Permit Information
Permit NumberFIR17-00700
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 1424 W FRONT ST
Project NameVerasso 8-plex
Customer Number 
ePlanReviewYes
Description
[Verasso 8-Plex]
The fire sprinkler scope of work consists of protecting an 8-plex apartment building using a NFPA 13R sprinkler system. The system utilizes CPVC piping and residential sprinklers spaced at 18’x18’.

[BLD17-01499]
Permit for the construction of an 8 unit, 2 story wood-framed apartment building with work to include general site work and construction of the new building per the approved plans. Special inspections required for structural steel AISC360, Concrete Construction Post installed anchors, and soils. This building is fire sprinklered with an NFPA-13R system. JAR

Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/27/20187/30/20187/30/2018PPASS
DetailsJim Page
Final fire sprinkler inspection complete.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Final Inspection7/26/20187/27/20187/27/2018PCANC
DetailsTroy Cobbley
No water on system so fire alarm contractor could not pre-test or test with me.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Final Inspection7/18/20187/19/20187/19/2018PFAIL
DetailsJim Page
Three fire sprinklers are to close to the ceiling fans, at least 36 inches is required. Five of the dry sidewalls on level 1 are to close to the deck, sidewall heads need to be 4 to 6 inches down from the ceiling.

If at possible we would like to have this Thursday afternoon. Thank you!
Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in/Hydro5/24/20185/25/20185/25/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauges for levels 1 and 2.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in3/13/20183/13/20183/13/2018PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
INSP-Sprinkler Rough-in3/5/20183/5/20183/5/2018PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 2 complete, level 2 approved for cover.
INSP-Sprinkler Rough-in2/26/20182/27/20182/27/2018AFAIL
DetailsTroy Cobbley
Todays inspection was for the second floor. I noted that the piping and pendant heads had not been installed where shown on the plans. This caused heads to be overspaced off walls, blocked by walls and located too close to each other in many locations. I also noted that the insulation needs to be "pocketed" around the piping to the dry sidewall heads in many locations and it also needs to be placed above the piping in several locations. I also noted a lack of coverage in the lobby area on the second floor and the first floor that Jim Danes is going to address. Also additional fittings have been added in to the gridded system that will need to be verified with hydraulic calculations to the plan reviewer.


2nd Floor Rough In Cover. Thank you! Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in2/26/20182/26/20182/26/2018PFAIL
DetailsTroy Cobbley
No city approved plans or notes on site. No inspection performed.

Can we please have a Rough In Cover on the 2nd Floor today please. Thank you! Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in2/15/20182/16/20182/16/2018PFAIL
DetailsJim Page
Check head spacing throughout project to veirfy proper distance from walls. Hangers will need to be adjusted/added throughout project. FDC piping will need to be completed before FDC can be covered. Cover for overhead fire sprinkler piping is not approved.
INSP-Sprinkler Rough-in2/9/20182/12/20182/9/2018ACANC
DetailsJim Page
1st Floor Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
PLANS/APPL TAKEN TO FRONT DESK  12/12/2017 DONE
as per Tim F-ok to send to front desk
Permit Ready to Issue  12/12/2017 DONE
Issue and Print Permit  12/12/2017 DONE
Intake Approval  12/8/2017 PASS
Plan assigned to (Tim)12/8/2017 12/8/2017 DONE
DetailsTim Frost
Application received  11/30/2017 DONE
Application submitted via PDS Online on Nov 30 2017 1:47PM