INSP-Final Inspection | 1/25/2019 | 1/25/2019 | 1/25/2019 | P | PASS |
Lee G Meredith
|
|
|
All systems tested 11/14/18. Issues with sync on that date were resolved by Steve Bingham PE performance testing that has since been approved on 1-25-19 by Ron Johnson.
|
DOC - Permit Finaled | | | 1/25/2019 | | PASS |
Lee G Meredith
|
|
|
|
INSP-Alarm Testing | 11/14/2018 | 11/14/2018 | 11/14/2018 | A | FAIL |
Lee G Meredith
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
On site 9:30 am with Nathan. Tested unit detectors and sounder for floors 2 - 5. Rooms requiring retest include 207,8,9,16, 315, 408, 503 and 506. Still to test is general alarm notification, corridor detection, manual alarm, all devices on 1st floor and garage, elevator recall and shunt, central station monitoring and batteries. Room on 1st floor is missing a pull box cover. Waterflow devices are missing covers.
On site 4:30 - 7:00 pm with Nathan and Adam Bayne. All remaining items tested and functioned. During general alarm, dwelling unit audible notificaiton did not sync with common area audible notificaiton. 11-15-18 discussed this issue with Ron Johnson.
|
INSP-Alarm Testing | 11/12/2018 | 11/13/2018 | 11/13/2018 | A | FAIL |
Lee G Meredith
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
System not ready. Items tested were not consistently working properly.
|
Issue and Print Permit | | | 12/18/2017 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/15/2017 | | DONE |
|
|
|
|
Alarm Plan Check | 12/15/2017 | | 12/15/2017 | | PASS |
Lee G Meredith
|
|
|
All corrections made. Plans approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/15/2017 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 12/15/2017 | | DONE |
|
|
|
|
1st review completed | | | 12/11/2017 | | FAIL |
|
|
|
See 1st review comments.
|
Miscellaneous action | | | 12/11/2017 | | DONE |
|
|
|
Emailed review comments to Sean for corrections and resubmittal.
|
Application received | | | 12/8/2017 | | FAIL |
|
|
|
Application submitted via PDS Online on Dec 8 2017 8:42AM
On site 9:30 am with Nathan. Tested unit detection and sounders for floors 2 through 5. Rooms required retest include 207,8,9,16,315,408, 503 and 506. All floors corridor detection, general alarm notification, central station monitoring, batteries, elevator recall and shunt, floor 1 and garage not tested yet. Waterflow sensors need covers installed and junction box cover on one first floor not installed yet.
|
Plan assigned to (Lee) | 12/8/2017 | | 12/8/2017 | | DONE |
Lee G Meredith
|
|
|
|