INSP-Final Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete, as-builds will be submitted for modifications that were made to system.
|
INSP-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 | A | FAIL |
Troy Cobbley
|
|
|
Panel and devices passed, smoke and pull tested ok, phone lines tested ok, the 30cd ceiling mount near the facp needs to be relocated or adjusted to a 75cd, a strobe needs to be added in the area just outsside of the facp, as-builts are needed to show these changes, sprinkler devices not tested due to no sprinkler contractor on site. Randy is going to email verification of the signals sent.
FIR17-00727 Phone #: ###-#### Inspection requested via web by Bruce Sullivan
|
1st review completed | | | 12/13/2017 | | PASS |
|
|
|
|
Alarm Plan Check | 12/13/2017 | | 12/13/2017 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/13/2017 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 12/13/2017 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/13/2017 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 12/12/2017 | | 12/12/2017 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 12/12/2017 | | DONE |
|
|
|
Product data for the FACP and NAC panels was not provided. Manual alarm product data was corrupted. Requested Bruce resend these. Bruce sent the files. for some reason, the manual station does not import properly but it has been reviewed and approved. Model number is FMM-325A.
|
Application received | | | 12/11/2017 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 11 2017 2:45PM
|