Permit Information
Permit NumberFIR17-00733
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 5257 W FAIRVIEW AVE
Project NamePlaza 7 - Zelham
Customer Number 
ePlanReviewYes
Description
Fire alarm scope for this project reconfigures locations of audio/visual notification appliances for the floor 1 area involved in the TI for Zelham Inc. The fire alarm design also includes a resubmittal based on aging permit FIR08-00550 which was never finaled. Design of Basement and Floor 2 areas are based on the original 2008 plans and have been field verified for any changes. This work is associated with building permit BLD17-01548.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/30/20184/2/20184/2/2018APASS
DetailsTroy Cobbley
permit finaled

after 10am please // Zach Phone #: ###-####
INSP-Final Inspection3/29/20183/30/20183/30/2018AFAIL
DetailsTroy Cobbley
There were issues with the interconnection of the pressure switches and tamper switches. No actual testing was performed.

Zach Phone #: ###-####
Alarm Plan Check3/23/2018 3/23/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/23/2018 DONE
Plan modification approved with review comments.
Permit Ready to Issue  3/23/2018 DONE
Plan Mod Approved
DO NOT REISSUE
CHANGE STATUS TO (ISS)  3/23/2018 DONE
Miscellaneous action  3/22/2018 DONE
Solenoid model number is not on the approved product list. Emailed John to have him submit the correct product data. John confirmed with the manufacturer the solenoid model is approved and provided backup documentation from the manufacturer.
INSP-Final Inspection3/15/20183/16/20183/16/2018APART
DetailsTroy Cobbley
The sync'ing of the notification has been repaired/tested and passed. All manual pull stations have been tested, the smoke detector above the main facp has been tested.


Zack Phone #: ###-####
INSP-Final Inspection3/14/20183/15/20183/15/2018AFAIL
DetailsJim Page
Flow switches on wet system fire sprinkler risers worked correctly. Audio visual notification did not sync correctly, audio visual devices will need to be re-inspected.
INSP-Final Inspection3/14/20183/14/20183/14/2018PPART
DetailsTroy Cobbley
For todays inspection I verifed the elevator recall smoke and heat detectors and the single duct smoke detector in the basement. The rest of the time I spoke to Steve, the project superintendant, about the possibility for a temporary.

Zak Anderson - Technician Phone #: ###-#### Inspection requested via web by John Siewert
Permit Ready to Issue  3/12/2018 DONE
Plan Mod approved
DO NOT REISSUE
CHANGE STATUS TO (ISS)  3/12/2018 DONE
Plan Modification Accepted  3/9/2018 DONE
Alarm Plan Check3/9/2018 3/9/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/9/2018 DONE
Plan Modification for addition of preaction in server room approved. No additional review comments. This approval is dependant upon sprinkler review and approval of added pre-action system.
Miscellaneous action  3/8/2018 DONE
Workflow reopened so John can upload pre-action system changes in a plan mod.
INSP-Final Inspection2/28/20183/1/20183/1/2018AFAIL
DetailsTroy Cobbley
Todays inspection was a walk through. I verified the head end equipment. I noted that plans need to be resubmitted for a plan modification due to 14 guage wire being used where as 12 guage was submitted. Also there are additional notification devices needed and many devices that need to be relocated or candella increased. The second floor wall layout at the east end does not match the plans. There is an access controled egress lock on the second floor that will need connected to the fire alarm system or contact will need to be made to the building code official. No devices have been tested.

John Howard - Technician Phone #: ###-#### Inspection requested via web by John Siewert
Miscellaneous action  2/28/2018 DONE
As built drawings received. Due to the extent of changes, I emailed John to let him know that a resubmittal would be required. Also, I need documentation on the solenoid and relay that shows they are listed for the use and a solenoid service switch needs to be added.
INSP-Conference2/1/20182/1/20182/1/2018PDONE
DetailsTroy Cobbley
We dicussed strobe modifications in the first floor lobby and in the basement.


John Phone #: ###-####
Issue and Print Permit  12/18/2017 DONE
Plan assigned to (Lee)12/14/2017 12/14/2017 DONE
DetailsLee G Meredith
1st review completed  12/14/2017 PASS
Alarm Plan Check12/14/2017 12/14/2017 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/14/2017 DONE
Plans approved with review comments.
Permit Ready to Issue  12/14/2017 DONE
Application received  12/13/2017 DONE
Application submitted via PDS Online on Dec 13 2017 9:35AM