Permit Number | FIR17-00776 |
Status | Finaled |
Name |
SHILO AUTOMATIC SPRINKLER CO
|
Site Address |
11343 W PRESIDENT DR
|
Project Name | Innovative Air T.I. |
Customer Number | |
ePlanReview | Yes |
Description |
[Innovative Air TI]
The fire sprinkler scope of work consists of a new tenant in an existing warehouse building. The existing two dry systems will be converted into two wet systems. The existing sprinkler system has been re-calculated based on the new rack storage arrangement.
Location on Plan - Warehouse
Commodity - HVAC , Unit Heaters in wood boxes
Classification - III
Storage Type (rack, solid pile, etc.) - Racks (Single, Double Row)
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 20’
Ceiling Height - 41’
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - Yes (Not required but existing)
In Rack Sprinklers - No
Sprinkler Type - ELO-231 SIN TY5111
High Temperature Sprinklers Required - Yes
Applicable NFPA Section - T 16.2.1.3.2, F 16.2.1.3.2(c) Curve F,
F 16.2.1.3.4.1
Hydraulic Design Criterion - .42/2000
Hose Stream Requirements - 500
• Racking permit BLD17-04659 (Not reviewed at the time of this fire sprinkler review.)
[BLD17-04612]
Tenant Improvement of an existing Type II-B Sprinkled prefabricated metal building to warehouse and office space with a second floor addition within the office space area. Improvements include but are not limited to new window and door fenestration in the existing building, new exterior paint and metal and wood siding on the north elevation, new non-combustible interior wall framing and structural floor framing of steel and concrete pan deck for new second floor, restroom, office, conference, storage and break room areas, new mechanical, plumbing and electrical, modifications to the existing fire sprinkler and alarm system. Additional exterior improvements would include a paving overlay of the existing parking area, re-stripe and new landscape features.
Fire Protection Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
Alternative Materials and Methods:
• There are no AMM at this time.
|