INSP-Final Inspection | 1/26/2018 | 1/29/2018 | 1/29/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Call prior to going Phone #: 6810381 >> Inspection requested via mobile web by Doug Lessa
|
INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 | A | FAIL |
Troy Cobbley
|
|
|
Provide modification to the two strobes to provide coverage as discussed and marked on the plans. Provide proper placement of the duct smoke detectors as discussed and provide testing. The hood suppression system reported as alarm to the FACP but the alarm signals did not report off site. Provide as-builts of changes prior to a final sign off.
Call prior to going Phone #: 6810381 >> Inspection requested via mobile web by Doug Lessa
|
Miscellaneous action | | | 1/26/2018 | | DONE |
|
|
|
As built drawings received indicating changes required by inspector.
|
Plan assigned to (Lee) | 1/5/2018 | | 1/5/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 1/5/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 1/5/2018 | | 1/5/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/5/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 1/5/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/5/2018 | | DONE |
|
|
|
|
Application received | | | 1/4/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 4 2018 4:07PM
|