INSP-Final Inspection | 7/17/2018 | 7/18/2018 | 7/18/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. New duct detector and installation arrangement accepted by plan review
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 6/20/2018 | 6/21/2018 | 6/21/2018 | A | CANC |
Troy Cobbley
|
|
|
The duct detector housing issue has not been resolved.
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 6/7/2018 | 6/8/2018 | 6/8/2018 | A | FAIL |
Troy Cobbley
|
|
|
We tested the duct smoke detector for shutdown and it functioned but the issue is per Potter tech support this duct detector, DDA, is not for outdoor use. A different detector listed for outdoor use, maybe with an enclosure, is going to need to be submitted/approved/installed and tested.
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Plan assigned to (Lee) | 1/23/2018 | | 1/23/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 1/23/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 1/23/2018 | | 1/23/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/23/2018 | | DONE |
|
|
|
Quick permit approved. No review comments.
|
Permit Ready to Issue | | | 1/23/2018 | | DONE |
|
|
|
Met
|
Issue and Print Permit | | | 1/23/2018 | | DONE |
|
|
|
|
Application received | | | 1/22/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 22 2018 2:03PM
|