INSP-Final Inspection | 7/12/2018 | 7/13/2018 | 7/13/2018 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Final Inspection | 7/11/2018 | 7/12/2018 | 7/12/2018 | P | FAIL |
Troy Cobbley
|
|
|
Ceiling tile not installed yet. Interconnect with the fire alarm system was incorrect. Need forward flush test.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 6/27/2018 | 6/27/2018 | 6/27/2018 | P | PASS |
Troy Cobbley
|
|
|
Rough-in passed. Corrections made on overspaced sprinklers. Piping can be covered.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/25/2018 | 6/26/2018 | 6/26/2018 | A | PART |
Troy Cobbley
|
|
|
Pendant heads exceed 7' from wall in acouple locations. Final locations of these heads can be verified at final. Piping is ok for cover/rough-in passed.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Supply line flush | 2/9/2018 | 2/12/2018 | 2/12/2018 | A | CANC |
Troy Cobbley
|
|
|
Wrong permit number scheduled
|
INSP-Sprinkler Rough-in/Hydro | 2/9/2018 | 2/12/2018 | 2/12/2018 | A | CANC |
Troy Cobbley
|
|
|
Wrong permit number scheduled.
|
INSP-Sprinkler Rough-in | 2/9/2018 | 2/12/2018 | 2/12/2018 | P | CANC |
Troy Cobbley
|
|
|
Mike Martin is the contact for this inspection. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
Sprinkler Plan Check | 1/30/2018 | | 1/30/2018 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/30/2018 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 1/30/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/30/2018 | | DONE |
|
|
|
|
Application received | | | 1/25/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 25 2018 9:04AM
|
Intake Approval | | | 1/25/2018 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 1/25/2018 | | 1/25/2018 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 1/25/2018 | | 1/25/2018 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 1/25/2018 | | FAIL |
Tim Frost
|
|
|
|