Permit Information
Permit NumberFIR18-00057
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 7009 W FRANKLIN RD
Project NameBishop Kelly HS North Wing TI
Customer Number 
ePlanReviewYes
Description
[Bishop Kelly High School - North Wing] - Quick Permit
Add sprinkler below the added ceiling grid. follow the existing design.

[BLD17-00339]
(NORTH WING ADDITION) Construct a new 24,845 square foot science and technology classroom building on the existing Bishop Kelly High School campus. The addition will new classroom areas and a gathering area. Each of the classrooms and the gathering area are provided with additional exit doors directly to the exterior. This building is fully fire sprinklered for area increase and is fully alarmed. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/12/20187/13/20187/13/2018PPASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection7/11/20187/12/20187/12/2018PFAIL
DetailsTroy Cobbley
Ceiling tile not installed yet. Interconnect with the fire alarm system was incorrect. Need forward flush test.


Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro6/27/20186/27/20186/27/2018PPASS
DetailsTroy Cobbley
Rough-in passed. Corrections made on overspaced sprinklers. Piping can be covered.

Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in6/25/20186/26/20186/26/2018APART
DetailsTroy Cobbley
Pendant heads exceed 7' from wall in acouple locations. Final locations of these heads can be verified at final. Piping is ok for cover/rough-in passed.

Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Supply line flush2/9/20182/12/20182/12/2018ACANC
DetailsTroy Cobbley
Wrong permit number scheduled
INSP-Sprinkler Rough-in/Hydro2/9/20182/12/20182/12/2018ACANC
DetailsTroy Cobbley
Wrong permit number scheduled.
INSP-Sprinkler Rough-in2/9/20182/12/20182/12/2018PCANC
DetailsTroy Cobbley
Mike Martin is the contact for this inspection. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
Sprinkler Plan Check1/30/2018 1/30/2018 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  1/30/2018 DONE
DetailsTim Frost
Permit Ready to Issue  1/30/2018 DONE
Issue and Print Permit  1/30/2018 DONE
Application received  1/25/2018 DONE
Application submitted via PDS Online on Jan 25 2018 9:04AM
Intake Approval  1/25/2018 PASS
Plan assigned to (Tim)1/25/2018 1/25/2018 DONE
DetailsTim Frost
Sprinkler Plan Check1/25/2018 1/25/2018 FAIL
DetailsTim Frost
1st review completed  1/25/2018 FAIL
DetailsTim Frost