INSP-Final Inspection | 8/27/2018 | 8/28/2018 | 8/28/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 8/22/2018 | 8/23/2018 | 8/23/2018 | P | FAIL |
Jim Page
|
|
|
Notification did not sync or operate correctly, some devices worked, others did not, troubleshoot fire alarm system for proper operation.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Miscellaneous action | | | 8/23/2018 | | DONE |
|
|
|
As built drawing received and approved.
|
INSP-Final Inspection | 8/16/2018 | 8/16/2018 | 8/16/2018 | P | FAIL |
Troy Cobbley
|
|
|
As-builts are needed to show the two strobes that need their candella adjusted higher and the manual pull station that has been deleted. Several strobes I could not see the candella setting due to height and no ladder. No actual testing performed. Will need to be re-scheduled after as-builts are approved.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Plan resubmittals received | | | 5/1/2018 | | DONE |
|
|
|
|
1st review completed | | | 5/1/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 5/1/2018 | | 5/1/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/1/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 5/1/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/1/2018 | | |
|
|
|
|
Miscellaneous action | | | 4/16/2018 | | DONE |
|
|
|
Received architects comments to previous review comments. He indicated that previous work had proper notification and that these should still be adequate. Unfortunately, these devices are not shown on the current design and need to be there with calculations to insure proper coverage is still met. I emailed this information to Morgan.
|
Miscellaneous action | | | 4/6/2018 | | DONE |
|
|
|
Drawings still missing adequate notification in previously noted areas. Returned to Morgan for correction.
|
Plan resubmittals received | | | 4/5/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/26/2018 | | DONE |
|
|
|
Failed prescreen review. Returned to Morgan for Engineer of Record review and approval.
|
Application received | | | 1/25/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 25 2018 2:04PM
|