Permit Information
Permit NumberFIR18-00059
StatusFinaled
Name PROTEX
Site Address 5246 W OVERLAND RD
Project NameStep Ahead T.I.
Customer Number 
ePlanReviewYes
Description
Add notification and air handler shutdown in new tenant space. This work is associated with building permit BLD17-03952.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/27/20188/28/20188/28/2018APASS
DetailsTroy Cobbley
Permit finaled

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection8/22/20188/23/20188/23/2018PFAIL
DetailsJim Page
Notification did not sync or operate correctly, some devices worked, others did not, troubleshoot fire alarm system for proper operation.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Miscellaneous action  8/23/2018 DONE
As built drawing received and approved.
INSP-Final Inspection8/16/20188/16/20188/16/2018PFAIL
DetailsTroy Cobbley
As-builts are needed to show the two strobes that need their candella adjusted higher and the manual pull station that has been deleted. Several strobes I could not see the candella setting due to height and no ladder. No actual testing performed. Will need to be re-scheduled after as-builts are approved.


Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  5/1/2018 DONE
1st review completed  5/1/2018 PASS
Alarm Plan Check5/1/2018 5/1/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/1/2018 DONE
Plans approved with review comments.
Permit Ready to Issue  5/1/2018 DONE
Issue and Print Permit  5/1/2018  
Miscellaneous action  4/16/2018 DONE
Received architects comments to previous review comments. He indicated that previous work had proper notification and that these should still be adequate. Unfortunately, these devices are not shown on the current design and need to be there with calculations to insure proper coverage is still met. I emailed this information to Morgan.
Miscellaneous action  4/6/2018 DONE
Drawings still missing adequate notification in previously noted areas. Returned to Morgan for correction.
Plan resubmittals received  4/5/2018 DONE
Miscellaneous action  1/26/2018 DONE
Failed prescreen review. Returned to Morgan for Engineer of Record review and approval.
Application received  1/25/2018 DONE
Application submitted via PDS Online on Jan 25 2018 2:04PM