INSP-Final Inspection | 10/17/2019 | 10/18/2019 | 10/21/2019 | A | PART |
Troy Cobbley
|
|
|
A life safety temp for the use of the two elevators is being given with boise fire permission with the states acceptance. The acceptance paperwork is attached to this permit. Per dicussion with Jim Shilton these elvators will still need to be re-inspected by the fire code inspector prior to a final sign off as discussed.
Phone #: ###-#### Inspection requested via web by Jim Shilton
|
INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 | A | FAIL |
Troy Cobbley
|
|
|
I witnessed the testing of the two heat detectors on the elevator penthouse, as marked on the plans, and they shunt the two elevators. I witnessed the penthouse smoke detector recall the eelvator to the 1st floor. We then went to the 9th floor and tripped the elevator lobby detector and the elevator did nothing and actually continued to function as normal.. Testing was stopped.
Please call me prior to arrival so we can prepare. State Elevator Inspector will make provisions to allow city to inspect permitted 2 new elevators.
Phone #: ###-#### Inspection requested via web by Jim Shilton
|
INSP-Final Inspection | 10/15/2019 | 10/16/2019 | 10/16/2019 | A | CANC |
Troy Cobbley
|
|
|
Call before please Thanks, Jim ###-#### Phone #: ###-#### >> Inspection requested via web by Jim Shilton Inspection cancelled from web by: Jim Shilton
|
INSP-Final Inspection | 7/16/2018 | 7/17/2018 | 7/16/2018 | A | CANC |
Jim Page
|
|
|
Chris Siewert - Technician Phone #: ###-#### >> Inspection requested via web by John Siewert Inspection cancelled from web by: John Siewert
|
Issue and Print Permit | | | 2/8/2018 | | DONE |
|
|
|
|
Application received | | | 2/7/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 7 2018 1:32PM
|
Plan assigned to (Lee) | 2/7/2018 | | 2/7/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 2/7/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 2/7/2018 | | 2/7/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/7/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 2/7/2018 | | DONE |
|
|
|
|