INSP-Final Inspection | 7/23/2019 | 7/24/2019 | 7/24/2019 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
Plan assigned to (Lee) | 6/21/2019 | | 6/24/2019 | | DONE |
Lee G Meredith
|
|
|
plan mod
|
1st review completed | | | 6/24/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 6/24/2019 | | 6/24/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/24/2019 | | DONE |
|
|
|
Passed. No additional comments.
|
Permit Ready to Issue | | | 6/24/2019 | | DONE |
|
|
|
plan mod please do not re issue
|
CHANGE STATUS TO (ISS) | | | 6/24/2019 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 6/21/2019 | | DONE |
|
|
|
per Dante A Frassa via email - plan mod
|
Permit Ready to Issue | | | 6/13/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/13/2019 | | DONE |
|
|
|
AS BUILT
|
Plan assigned to (Lee) | 6/10/2019 | | 6/12/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/12/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 6/12/2019 | | 6/12/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/12/2019 | | DONE |
|
|
|
As built - No Fee
|
Plan Modification Accepted | | | 6/10/2019 | | DONE |
|
|
|
as built
|
INSP-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 | A | FAIL |
Jim Page
|
|
|
Exterior access control for staiwell doors did not release on general alarm, per IFC access control doors in egress paths need to disable and unlock on general fire alarm.
|
INSP-Final Inspection | 5/14/2019 | 5/17/2019 | 5/17/2019 | A | PART |
Jim Page
|
|
|
Final inspection for all initiating devices complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 5/14/2019 | 5/16/2019 | 5/16/2019 | A | PART |
Jim Page
|
|
|
All associated fire alarm items for elevator recall/shunt complete. Notification inspection for all areas of building complete. Last remaining items to inspect is initiating devices not associated with the fire sprinkler system.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 5/14/2019 | 5/15/2019 | 5/15/2019 | P | PART |
Jim Page
|
|
|
Testing for in-duct smoke detection and HVAC unit shutdown complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
Miscellaneous action | | | 3/11/2019 | | DONE |
|
|
|
Nathan emailed to ask if notification will be needed in the mechanical penthouse. Currently none is shown. I informed him that in hind sight, I should have indicated that audible notification will be required to meet a minimum of 15db above ambient no since this is not common or public, visible notification is not required. Added horn(s) can be shown on as built drawings.
|
Miscellaneous action | | | 5/23/2018 | | DONE |
|
|
|
Emailed Charlie to let him know that there will need to be alarm signals between the existing building and this building. Alarm conditions from either will need to transmit a relay signal to the other building that is to be received as a supervisory condition. This informaiton can be added to the as built drawings.
|
Issue and Print Permit | | | 5/23/2018 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/22/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 5/22/2018 | | 5/22/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/22/2018 | | DONE |
|
|
|
Plans approved with review comments. and requirements.
|
Permit Ready to Issue | | | 5/22/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 5/17/2018 | | DONE |
|
|
|
Emailed Adam to let him know drawings will be returned for corrections. Strobe candela needs to be shown at the device instead of a seperate spreadsheet.
|
Miscellaneous action | | | 3/23/2018 | | DONE |
|
|
|
Charlie Bayne added to eplanreview as a user on this project.
|
Plan assigned to (Lee) | 3/8/2018 | | 3/8/2018 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 3/8/2018 | | FAIL |
|
|
|
Failed pre-screen review. 14 drawings submitted as a single file. Returned to Sean and told him to submit each drawing as an individual file.
|
Miscellaneous action | | | 3/8/2018 | | DONE |
|
|
|
Emailed Sean to unform him that the engineer of record will need to sign off on the shop drawings prior to resubmittal.
|
Application received | | | 3/2/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 2 2018 11:19AM
|