Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR18-00180
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 8000 S FEDERAL WAY
Project NameMicron CUP 39-2
Customer Number 
ePlanReviewYes
Description
[Micron Building 39 CUP - C29420]
The fire sprinkler scope of work consists of a new wet system. The system is designed as a grid with a tree portion supplied from the main. This system only protects a portion of the building.

• The underground is under permit FIR17-00502
• See FIR17-00042, FIR18-00001 for other permits on this building.
• See addendum for graphic scope of work
[BLD17-01950]
The CUP 3 building (B39) will be located south of the new B51 R&D Expansion Project. This permit is for structural only for building and utility trestle footings, foundations and structural steel components of the total design. The proposed new CUP B39 is 68,000 square feet with a 9,319 sq. ft. equipment platform and is type IIB construction. Building occupancy groups consist of F1, H3, and H4. All work per the approved plans and attached engineering. Special inspections are required. This building is fully fire sprinklered for area increase. CDM

Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/29/20197/29/20197/29/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.

Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
Plan Modification Accepted  7/12/2019 DONE
per Jessica at Tribal Fire - start workflow for plan mod
Plan assigned to (Stumbaugh)7/12/2019 7/12/2019 DONE
DetailsMark Stumbaugh
plan mod
Sprinkler Plan Check7/12/2019 7/12/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  7/12/2019 DONE
DetailsMark Stumbaugh
Plan Mod Fee $150.00
Permit Ready to Issue  7/12/2019 DONE
plan mod so please don't re issue
CHANGE STATUS TO (ISS)  7/12/2019 DONE
INSP-Final Inspection7/2/20197/3/20197/3/2019AFAIL
DetailsJim Page
Notated city approved drawings areas that need to be corrected. Submit plan modification to have sway bracing removed from city approved drawings.

Please call Dillion Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection6/25/20196/25/20196/25/2019PCANC
DetailsJim Page
No inspection performed for this permit due to time constraints, this request is cancelled per conversation with point of contact.

Please call Dillion Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection6/18/20196/19/20196/19/2019ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.

Dillion Phone #: ###-####
INSP-Final Inspection4/12/20194/12/20194/12/2019PCANC
DetailsJim Page
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection7/30/20187/31/20187/31/2018PPART
DetailsJim Page
Final fire sprinkler inspection complete, fire sprinkler permit will remain in issued status until project is complete due to possible obstructions needing coverage.

Chris Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro6/15/20186/18/20186/18/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.

Chris Phone #: ###-####
Fees Due Hold4/13/2018 6/15/2018 DONE
DetailsCandy A. Nichols
Fees Due Hold3/15/2018 4/12/2018 DONE
DetailsChristina Prado
Sprinkler Plan Check3/14/2018 3/14/2018 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  3/14/2018 DONE
DetailsTim Frost
Permit Ready to Issue  3/14/2018 DONE
Met
Issue and Print Permit  3/14/2018 DONE
Sprinkler Plan Check3/13/2018 3/13/2018 FAIL
DetailsTim Frost
Miscellaneous action  3/13/2018 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Sprinkler Plan Check3/12/2018 3/12/2018 FAIL
DetailsTim Frost
Miscellaneous action  3/12/2018 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Sprinkler Plan Check3/9/2018 3/9/2018 FAIL
DetailsTim Frost
Please, see attached comments.
1st review completed  3/9/2018 FAIL
DetailsTim Frost
Intake Approval  3/8/2018 PASS
Plan assigned to (Tim)3/8/2018 3/8/2018 DONE
DetailsTim Frost
Miscellaneous action  3/8/2018 PEND
Sent the following email on 3/08/2018

Clarence,

• I see an area on the drawing indicated as “Sulfuric Acid Storage”. Please, provide the quantities and how it is being stored.
• Sulfuric Acid is a class 2 water-reactive substance. I will need a letter verifying sprinkler protection is permissible and desired from the owner's engineer.
• There is another area which is indicated as “90 Day Accumulation”. Accumulation of what? What is the quantity and how is it being stored.
• Why is the area between columns SD.8- SH, S8-S8,7 NOT being protected? The fire main required protection per NFPA 13: 8.16.4.3.1, 8.16.4.3.2

The above information is required before the review can be completed.
Application received  3/6/2018 DONE
Application submitted via PDS Online on Mar 6 2018 2:43PM