INSP-Final Inspection | 3/22/2018 | 3/26/2018 | 3/26/2018 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
|
Telephone call | | | 3/22/2018 | | DONE |
|
|
|
Ken called to inform me that the owner has elected to go with Local Fire and Security for central station monitoring so ken will be submitting as built drawing that remove the dialer originally shown. Local Fire and Security is now providing this service and has installed equipment. I emailed Brian to inform him he will need to apply for a permit. Mary Froemke called to note that the original communicator was never removed and that it will be reused. Therefore, no new permit will be required by Local. Buildings A-J were installed in 2016 under permit numbers FIR16-00172 through 00181.
|
Issue and Print Permit | | | 3/15/2018 | | DONE |
|
|
|
|
1st review completed | | | 3/14/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 3/14/2018 | | 3/14/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/14/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 3/14/2018 | | DONE |
|
|
|
Met
|
Plan assigned to (Lee) | 3/12/2018 | | 3/12/2018 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 3/12/2018 | | DONE |
|
|
|
Emailed Ken requesting more informaiton on his heated enclosure. Asked if it was a packaged unit or hand built from parts. Missing numerous product data sheets. Also asked if the panel will be mounted in the sunlight. If so, it will need cooling too. He responded to say that it was built from Hoffman approved parts for outside enclosures that require heat and ventilation. The panel will not be located in sunlight.
|
Application received | | | 3/11/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 11 2018 11:38AM
|