INSP-Final Inspection | 3/11/2019 | 3/11/2019 | 3/11/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, as-builts have been approved. Final inspection for AES complete.
bill Phone #: ###-####
|
Miscellaneous action | | | 3/11/2019 | | DONE |
|
|
|
As built drawing now shows a Simplez 4001 panel with alarm and trouble. Appears to be correct and ready for inspection.
|
INSP-Final Inspection | 3/8/2019 | 3/8/2019 | 3/8/2019 | P | CANC |
Jim Page
|
|
|
Does not appear as-builts have been reviewed per activities under this permit. After discussion with point of contact, inspection request will be rescheduled for a later date, this request is cancelled per conversation with POC.
Bill Phone #: ###-####
|
(F) Reprint permit | | | 3/8/2019 | | DONE |
|
|
|
|
INSP-Final Inspection | 3/6/2019 | 3/6/2019 | 3/6/2019 | P | FAIL |
Troy Cobbley
|
|
|
Alarmco's as-builts showed wrong panel. tested signal. panel trouble relay does not latch and resets when silenced. signals report. To final permit ad-builts needed.
call ahead // bill Phone #: ###-####
|
INSP-Final Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Bill Phone #: ###-####
|
Miscellaneous action | | | 3/5/2019 | | DONE |
|
|
|
Lori requested eplanreview work flow be opened to upload as built drawings.
|
Case Summary | | | 6/20/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/26/2018 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 3/13/2018 | | 3/13/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/13/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 3/13/2018 | | 3/13/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/13/2018 | | DONE |
|
|
|
Quick permit approved with drawing notes. No review comments.
|
Permit Ready to Issue | | | 3/13/2018 | | DONE |
|
|
|
met
|
Application received | | | 3/12/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 12 2018 8:03PM
|