INSP-Final Inspection | 3/28/2018 | 3/28/2018 | 3/28/2018 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 3/20/2018 | 3/27/2018 | 3/27/2018 | A | FAIL |
Troy Cobbley
|
|
|
Need a 12ah battery as per plans
|
Miscellaneous action | | | 3/27/2018 | | DONE |
|
|
|
Mary submitted a revised riser that shows an 8ah battery in place of the original 12ah. Product data indicates 10-12ah is required. I informed Mary that 8ah is not acceptable. She replied to indicate that a 12ah would be supplied to match the original submittal.
|
Plan assigned to (Lee) | 3/16/2018 | | 3/16/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/16/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 3/16/2018 | | 3/16/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/16/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 3/16/2018 | | DONE |
|
|
|
Met
|
Issue and Print Permit | | | 3/16/2018 | | DONE |
|
|
|
|
Application received | | | 3/15/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 15 2018 6:02PM
|