Permit Information
Permit NumberFIR18-00233
StatusFinaled
Name NORTHWEST FIRE AND SECURITY
Site Address 8100 W EMERALD ST
Project NamePFCU SUITE 170 PREACTION PANEL
Customer Number 
ePlanReviewYes
Description
ADD A PREACTION RELEASING PANEL FOR IT ROOM. This work is associated with building permit BLD17-03590.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/9/20184/9/20184/9/2018PPASS
DetailsJim Page
Final fire alarm inspection for scope of work complete.
Issue and Print Permit  3/27/2018 DONE
Plan resubmittals received  3/26/2018 DONE
1st review completed  3/26/2018 PASS
Alarm Plan Check3/26/2018 3/26/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/26/2018 DONE
Plans approved with review comments.
Permit Ready to Issue  3/26/2018 DONE
Miscellaneous action  3/22/2018 DONE
Broadie Stenquist sent product data on the listed assembly they are providing. It appears the included solenoid is not approved to be used with the Siemens panel. Informed Rick of this and told him the application is being rejected.
1st review completed  3/22/2018 FAIL
Siemens panel is not compatible with the solenoid provided in the listed pre-action assembly from Treasure Valley Fire Protection. Rick notified by email.
Telephone call  3/21/2018 DONE
Rick called to inform me that he didn not have the model number for the solenoid. He did email product data that indicated which solenoids were listed with the panel model he submitted. I emailed Brodie at TVFP requesting the solenoid model number since they are supplying it.
Application received  3/20/2018 DONE
Application submitted via PDS Online on Mar 20 2018 12:55PM
Miscellaneous action  3/20/2018 DONE
Solenoid product data not provided. Requested this information from Rick.
Plan assigned to (Lee)3/20/2018 3/20/2018 DONE
DetailsLee G Meredith