Description
THIS PROJECT SCOPE IS TO TIE A NEW AES INTELLINET RF COMMUNICATOR TO THE EXISTING MAXSYS FIRE ALARM COMMUNICATOR IN ORDER TO ELIMINATE TELEPHONE LINES AT THE SITE.
This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/2/20194/3/20194/3/2019PPASS
DetailsJim Page
Final AES inspection complete.

as late in pm as possible - can't have alarms go off during school // Will Phone #: ###-####
Fees Due Hold3/23/2019 4/2/2019 DONE
DetailsBrittany Hill
INSP-Final Inspection3/22/20193/22/20193/22/2019PFAIL
DetailsJim Page
Trouble restores with monitoring when a general fire alarm is sent even though fire panel is still in trouble.

Bill Phone #: ###-####
Fees Due Hold3/22/2019 3/22/2019 DONE
DetailsJudith Amador
INSP-Final Inspection3/20/20193/21/20193/21/2019AFAIL
DetailsJim Page
Valve on fire sprinkler system reports out as a trouible, when fire alarm panel is in trouble, each subsequent trouble does not report out until panel is reset.

Bill Phone #: ###-####
INSP-Final Inspection3/14/20193/15/20193/15/2019AFAIL
DetailsJim Page
AES did not show NETCON 5.

Jacob Phone #: ###-####
INSP-Final Inspection3/14/20193/14/20193/14/2019PFAIL
DetailsJim Page
Put panel into trouble, trouble signal was recieved at central station, sent a general alarm and trouble restored at central station. Issue needs to be resloved and panel needs to be tested with real events and not shorting contacts.

Jacob Phone #: ###-####
Miscellaneous action  3/11/2019 DONE
Workflow opened for as built upload
Miscellaneous action  3/11/2019 DONE
As built approved, subject to inspectors functional test and comparison of as builts to actual installation.
Case Summary  6/20/2018 DONE
Issue and Print Permit  4/26/2018 DONE
Plan assigned to (Lee)3/21/2018 3/21/2018 DONE
DetailsLee G Meredith
1st review completed  3/21/2018 PASS
Alarm Plan Check3/21/2018 3/21/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/21/2018 DONE
Quick permit approved as noted. No review comments.
Permit Ready to Issue  3/21/2018 DONE
met
Application received  3/20/2018 DONE
Application submitted via PDS Online on Mar 20 2018 7:52PM