Permit Information
Permit NumberFIR18-00258
StatusFinaled
Name LOCAL FIRE AND SECURITY
Site Address 1055 N CURTIS RD
Project NameSARMC CT #2 Remodel
Customer Number 
ePlanReviewYes
Description
Initiating devices will be removed within the TI so the ceiling tiles can be replaced. Upon completion of the ceiling, the existing devices will be reinstalled in their same locations and tested per NFPA 72. This work is associated with building permit BLD17-04482.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/22/20191/23/20191/23/2019APASS
DetailsJim Page
Final fire alarm inspection for area of work complete.

Brian Phone #: ###-####
INSP-Final Inspection5/10/20185/11/20185/11/2018ACANC
DetailsTroy Cobbley
Simplex has not performed their portion of work per Brian Anderson. The system is not ready for testing

Brian Phone #: ###-####
INSP-Final Inspection4/5/20184/6/20184/6/2018APART
DetailsTroy Cobbley
Phase one (CT#2 Room/Control Room) fire alarm work is complete except there is a audible sync issue and it appears that a visual sync issue. The sync issues will need to be addressed prior to a final sign off.

Brian Phone #: ###-####
Issue and Print Permit  4/3/2018 DONE
(F) Reprint permit  4/3/2018 DONE
Plan resubmittals received  3/30/2018 DONE
1st review completed  3/30/2018 PASS
Alarm Plan Check3/30/2018 3/30/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/30/2018 DONE
Quick permit approved. No review comments.
Permit Ready to Issue  3/30/2018 DONE
Application received  3/28/2018 DONE
Application submitted via PDS Online on Mar 28 2018 9:25AM
Plan assigned to (Lee)3/28/2018 3/28/2018 DONE
DetailsLee G Meredith
Miscellaneous action  3/28/2018 DONE
Failed prescreen review. Needs candela and scale graph shown. Audible notification is not shown. Returned to Mary and emailed her the deficiencies.