INSP-Final Inspection | 5/16/2019 | 5/17/2019 | 5/17/2019 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection complete.
Justin Phone #: ###-####
|
INSP-Conference | 5/2/2019 | 5/3/2019 | 5/3/2019 | A | DONE |
Troy Cobbley
|
|
|
We spoke about cordination of Vesda inspection and final sprinkler inspecton in regards to ceiling tile installation. Project walk, expectations for close out // Justin Phone #: ###-####
|
INSP-Final Inspection | 4/5/2019 | 4/9/2019 | 4/9/2019 | A | PART |
Jim Page
|
|
|
All fire alarm components associated with the fire sprinkler system has been tested, all devices tested satisfactorily.
THIS IS AN ALARM FINAL SO IT WILL TAKE A COUPLE HOURS. WE WILL CALL IN ANOTHER FINAL LATER WHEN ALL THE CEILING TILES ARE IN. Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
INSP-Sprinkler Rough-in/Hydro | 4/8/2019 | 4/8/2019 | 4/8/2019 | P | CANC |
Jim Page
|
|
|
|
INSP-Sprinkler Rough-in | 3/27/2019 | 3/27/2019 | 3/27/2019 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping on levels 4 and 5 complete, approved for cover. All rough to cover inspections complete.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 3/27/2019 | 3/27/2019 | 3/27/2019 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for east side standpipe, level 4 and level 5 to include penthouse witnessed, no pressure loss observed.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 3/21/2019 | 3/22/2019 | 3/22/2019 | P | CANC |
Jim Page
|
|
|
Time trip tests for LL3, LL2 dry systems. Please call Jeff with time frame. Phone #: ###-#### >> Inspection requested via web by Jeff Packham Inspection cancelled from web by: Jeff Packham
|
INSP-Sprinkler Rough-in | 3/13/2019 | 3/14/2019 | 3/14/2019 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for the remaining overhead fire sprinkler piping on level 3 complete, all of level 3 approved for cover. Overhead fire sprinkler piping above hardlids next to sky bridge inspected, piping above hardlids in inspected areas approved for cover.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 3/13/2019 | 3/14/2019 | 3/14/2019 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for three dry systems witnessed, no pressure loss observed.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 3/6/2019 | 3/7/2019 | 3/7/2019 | P | PART |
Jim Page
|
|
|
Partial rough to cover inspection for overhead fire sprinkler piping on level 3 complete, notated city approved drawings with areas approved for cover. Remaining sprinkler piping on level 2 inspected, all of level 2 approved for cover.
JUSTIN Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 3/6/2019 | 3/7/2019 | 3/7/2019 | P | PART |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping on level 3 witnessed, no pressure loss observed.
JUSTIN Phone #: ###-####
|
INSP-Sprinkler Rough-in | 3/4/2019 | 3/5/2019 | 3/5/2019 | P | PART |
Jim Page
|
|
|
Fire pump commissioning complete.
fire pump test // justin Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 2/22/2019 | 2/22/2019 | 2/22/2019 | P | PART |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping on level 2 witnessed, no pressure loss observed.
|
INSP-Sprinkler Rough-in | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | PART |
Jim Page
|
|
|
Partial rough to cover inspection for overhead fire sprinkler piping on level 2 complete, notated city approved drawings with red in areas approved for cover.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 2/20/2019 | 2/21/2019 | 2/21/2019 | A | PART |
Jim Page
|
|
|
Hydrostatic yesy for pump room, west standpipe and level 1 witnessed, no pressure loss observed.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 | A | PART |
Jim Page
|
|
|
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings on level 1 with yellow highlighter/red ink areas approved for cover.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 11/6/2018 | 11/7/2018 | 11/7/2018 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for the area in the lower level of the parking garage where piping is ok for cover.
cover // Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 10/31/2018 | 10/31/2018 | 10/31/2018 | P | PART |
Jim Page
|
|
|
Partial rough to cover inspection for overhead fire sprinkler piping above hardlid on 1st lower parking level complete, overhead fire sprinkler piping at base of ramp on 1st lower level approved for cover.
of Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in | 9/12/2018 | 9/13/2018 | 9/13/2018 | A | PASS |
Adele J Schaffeld-Griffin
|
|
|
Inspection Comments from Forrest-Overhead rough in approved for cover at first floor sheetrock ceilings per plan annotations. Refer to stamped plan set, sheet FP8 for locations and dated remarksTHIS IS A ROUGH IN FOR HARD LIDS ON 1st FLOOR. TOM SMALL IS OUR SITE CONTACT Phone #: ###-#### >> Inspection requested via web by Brad Bettencourt
|
INSP-Sprinkler Rough-in | 8/29/2018 | 8/30/2018 | 8/30/2018 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for 2nd floor locations (clouds) where sprinkler piping can be covered. Marked "OK" in red.
Justin Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 8/14/2018 | 8/16/2018 | 8/16/2018 | A | PASS |
Jim Page
|
|
|
24 hour air test complete for dry systems in fire pump room.
JUSTIN IS OUR CONTACT THIS IS TO FINISH THE (3) 24 HOUR AIR TEST FOR THE DRY SYSTEMS IN THE PARKING LEVELS Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
INSP-Sprinkler Rough-in | 8/15/2018 | 8/15/2018 | 8/15/2018 | P | PART |
Jim Page
|
|
|
Rough in inspection for overhead fire sprinkler piping in parking garage levels B3, B2, and B1 to include level 1 wet system.
|
INSP-Sprinkler Rough-in/Hydro | 8/14/2018 | 8/15/2018 | 8/15/2018 | A | PART |
Jim Page
|
|
|
24 hour air test started at 11AM with 41 PSI on each system.
JUSTIN IS OUR CONTACT THIS IS A ROUGH-IN AND THE START OF (3) 24 HOUR AIR TEST FOR THE DRY SYSTEMS IN THE PARKING LEVELS Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
Miscellaneous action | | | 4/6/2018 | | DONE |
|
|
|
**** FIELD INSPECTOR ***
The pump curve is insufficent. Do not perform the pump test or inspection until a decent curve is provided.
|
Sprinkler Plan Check | 4/6/2018 | | 4/6/2018 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/6/2018 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 4/6/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/6/2018 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/3/2018 | | 4/3/2018 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 4/3/2018 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 4/3/2018 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 3/30/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 30 2018 2:25AM
|
Intake Approval | | | 3/30/2018 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 3/30/2018 | | 3/30/2018 | | DONE |
Tim Frost
|
|
|
|