Permit Information
Permit NumberFIR18-00282
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 980 N MILWAUKEE
Project NameMAGNIFICENT GARDEN TI
Customer Number 
ePlanReviewYes
Description
[Magnificent Garden Restaruant TI] - Quick Permit
Add, plug and relocate sprinklers to accommodate new wall and ceiling configuration.

[BLD17-04653]
The fire sprinkler system is used for fire area. Demolition work includes removing the existing restrooms, some interior shear walls, and interior finishes. To remodel an existing 7,504 square foot restaurant building for a new restaurant tenant. New shear walls will be constructed. Work relating to the shear walls includes concrete footings, wood stud, structural sheathing, drag strut, and hold downs. Special Inspection is required for anchors post-installed in hardened concrete. A new ground supported make-up air unit with new ducting on the roof will provide make-up air for the cooking exhaust systems. Work includes interior nonbearing walls, 2 multi-user toilet rooms accessible to the disabled, a raised sleeper floor system at the restrooms, interior doors, a bar, a reflecting pool water feature, a planter, and finishes. Each table will have its own table top grill system with a downdraft grease hood and duct system. A total of 7 systems are proposed for the dining area (50 hoods total). Each system shall be provided with a fire suppression system. Exhaust fans will be provided on the roof. Horizontal and vertical grease ducts will have a two layer 1-hr fire-resistance-rated duct wrap system installed on the outside of the ducts. Existing grease hoods in the kitchen and their make-up air units will remain and will be reused. Existing roof top HVAC units for space conditioning will remain and be reused. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/18/20194/18/20194/18/2019PPASS
DetailsJim Page
Final fire sprinkler inspection complete.

Rick Phone #: ###-####
INSP-Sprinkler Rough-in4/12/20194/15/20194/16/2019PCANC
DetailsTroy Cobbley
rick Phone #: ###-####
INSP-Sprinkler Rough-in4/12/20194/15/20194/15/2019APASS
DetailsTroy Cobbley
Rough-in passed. Piping can be covered in the Kitchen area.


Please call Roy with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Sprinkler Rough-in10/23/201810/24/201810/24/2018APASS
DetailsTroy Cobbley
Columns and soffit are filled with non-combustilbe insulation and can be covered.

Rick Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro8/2/20188/3/20188/3/2018APASS
DetailsTroy Cobbley
See the city approved plans for locations where the sprinkler piping can be covered as marked "ok" in red. I noted a combustible concealed space that will need addressed before a final inspection will be passed.


Rick Phone #: ###-####
Issue and Print Permit  4/9/2018 DONE
Intake Approval  4/6/2018 PASS
Plan assigned to (Tim)4/6/2018 4/6/2018 DONE
DetailsTim Frost
Sprinkler Plan Check4/6/2018 4/6/2018 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  4/6/2018 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  4/6/2018 DONE
DetailsTim Frost
Permit Ready to Issue  4/6/2018 DONE
Application received  4/5/2018 DONE
Application submitted via PDS Online on Apr 5 2018 11:37AM