Permit EXPIRED | | | 2/21/2019 | | DONE |
|
|
|
as per Troy Cobbley-expire this permit because Viking Auto pulled a new permit FIR18-00429 instead of doing a plan mod-so see FIR18-00429 for inspections
|
INSP-Final Inspection | 5/7/2018 | 5/8/2018 | 5/8/2018 | A | FAIL |
Troy Cobbley
|
|
|
The plans indicate that the area around the new room is Office. It is actually being used for Ordinary Hazard. So plans need to be resubmitted changing the sprinkler spacing from light to ordinary hazard. Also two of the four pendant heads in the new room are utilizing "flex heads" these need to be addressed as well.
Roy Phone #: ###-####
|
Sprinkler Plan Check | 4/23/2018 | | 4/23/2018 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/23/2018 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 4/23/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/23/2018 | | DONE |
|
|
|
|
Intake Approval | | | 4/19/2018 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 4/19/2018 | | 4/19/2018 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 4/17/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 17 2018 3:34PM
|