DOC - Permit Finaled | | | 11/25/2019 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/7/2018 | | DONE |
|
|
|
As built drawings received but revised calcs missing. Emailed Nathan requesting them.
Corrected as built drawings received 11-25-19.
|
INSP-Final Inspection | 6/6/2018 | 6/6/2018 | 6/6/2018 | P | CANC |
Troy Cobbley
|
|
|
Still waiting on the outcome of the as-built plans.
As late as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 6/4/2018 | 6/5/2018 | 6/5/2018 | A | FAIL |
Troy Cobbley
|
|
|
Will be ok to final when the as-builts have been accepted.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 6/3/2018 | 6/4/2018 | 6/4/2018 | A | FAIL |
Troy Cobbley
|
|
|
For todays inspection I went through equipment and verified notification device spacing. The candella needs to be changed on several devices and atleast two devices added. We need to test the notification circuit, sprinkler devices and duct smoke detectors. As-builts will be needed as well.
Phone #: ###-#### Inspection requested via web by Nathan Price
|
Plan resubmittals received | | | 5/9/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 5/9/2018 | | 5/9/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/9/2018 | | DONE |
|
|
|
Resubmittal approved with review comments.
|
Permit Ready to Issue | | | 5/9/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/9/2018 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 5/3/2018 | | 5/3/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/3/2018 | | FAIL |
|
|
|
See 1st review comments.
|
Miscellaneous action | | | 5/3/2018 | | DONE |
|
|
|
Called Charlie Bayne to discuss design deficiencies. Emailed him a copy of the review comments.
|
Application received | | | 4/25/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 25 2018 2:10PM
|