DOC - Permit Finaled | | | 11/20/2019 | | DONE |
|
|
|
Kitchen hood was actually removed prior to occupancy. System was fully tested on 3/5/19 and accepted during FIR18-00214 acceptance test.
|
INSP-Final Inspection | 5/24/2018 | 5/25/2018 | 5/25/2018 | P | PART |
Jim Page
|
|
|
Operational inspection for ductless hood fire suppression system complete, interface with fire alarm panel will be completed when core and shell fire alarm upgrade is complete. Permit will remain in issued status until fire alarm interface inspection completion.
Dave Phone #: ###-####
|
INSP-Final Inspection | 5/24/2018 | 5/24/2018 | 5/24/2018 | P | FAIL |
Jim Page
|
|
|
Fan and lights in cooking area of hood did not shut down on fire system activation.
|
INSP-Conference | 4/30/2018 | 4/30/2018 | 4/30/2018 | P | DONE |
Jim Page
|
|
|
Fire conference complete, manual pull for hood system will be installed on south wall as discussed.
|
Issue permit | | | 4/27/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/27/2018 | | DONE |
|
|
|
This permit was created on the web by Kenny Leslie
|