INSP-Final Inspection | 11/14/2018 | 11/15/2018 | 11/15/2018 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 | P | FAIL |
Troy Cobbley
|
|
|
Could not test the flow switch for the large system due to missing inspectors test orfice. All other devices worked and reported correctly.
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 11/9/2018 | 11/13/2018 | 11/13/2018 | A | DONE |
Lee G Meredith
|
|
|
Contact is Sean. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
System not ready for test. Sprinkler tamper showing active when all valves were open.
|
INSP-Final Inspection | 11/6/2018 | 11/7/2018 | 11/7/2018 | P | CANC |
Troy Cobbley
|
|
|
No permit can be found for the AES dialer. No testing performed until the communication is approved.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 10/22/2018 | 10/23/2018 | 10/23/2018 | A | CANC |
Troy Cobbley
|
|
|
Contact is Sean. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
Dialer not ready yet.
|
Miscellaneous action | | | 7/19/2018 | | DONE |
|
|
|
Previously planned fire alarm panel has been discontinued. Robe sent product data for the model 6700. This has been determined to be an acceptable replacement. Resubmittal is not required. Product data has been imported into eplanreview.
|
Plan assigned to (Lee) | 5/2/2018 | | 5/2/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/2/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 5/2/2018 | | 5/2/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/2/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 5/2/2018 | | DONE |
|
|
|
All requirements met
|
Issue and Print Permit | | | 5/2/2018 | | DONE |
|
|
|
|
Application received | | | 4/27/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 27 2018 11:32AM
|