Permit Information
Permit NumberFIR18-00333
StatusFinaled
Name PROTEX
Site Address 367 N ANCESTOR PL
Project NameEpisciences
Customer Number 
ePlanReviewYes
Description
Add a code-compliant fire alarm system to new construction for the purpose of sprinkler monitoring. This work is associated with building permit BLD17-03648.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/14/201811/15/201811/15/2018PPASS
DetailsTroy Cobbley
permit finaled


Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection11/13/201811/14/201811/14/2018PFAIL
DetailsTroy Cobbley
Could not test the flow switch for the large system due to missing inspectors test orfice. All other devices worked and reported correctly.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten


Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection11/9/201811/13/201811/13/2018ADONE
DetailsLee G Meredith
Contact is Sean. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten

System not ready for test. Sprinkler tamper showing active when all valves were open.
INSP-Final Inspection11/6/201811/7/201811/7/2018PCANC
DetailsTroy Cobbley
No permit can be found for the AES dialer. No testing performed until the communication is approved.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection10/22/201810/23/201810/23/2018ACANC
DetailsTroy Cobbley
Contact is Sean. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten

Dialer not ready yet.
Miscellaneous action  7/19/2018 DONE
Previously planned fire alarm panel has been discontinued. Robe sent product data for the model 6700. This has been determined to be an acceptable replacement. Resubmittal is not required. Product data has been imported into eplanreview.
Plan assigned to (Lee)5/2/2018 5/2/2018 DONE
DetailsLee G Meredith
1st review completed  5/2/2018 PASS
Alarm Plan Check5/2/2018 5/2/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/2/2018 DONE
Plans approved with review comments.
Permit Ready to Issue  5/2/2018 DONE
All requirements met
Issue and Print Permit  5/2/2018 DONE
Application received  4/27/2018 DONE
Application submitted via PDS Online on Apr 27 2018 11:32AM