INSP-Final Inspection | 6/11/2018 | 6/12/2018 | 6/12/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Ken Webster
|
Miscellaneous action | | | 6/8/2018 | | DONE |
|
|
|
Received as built drawings from Mary. Floor plan has changed since original drawings, according to as built. Mary is not sure why it is different. I told her this need to be accurate for the final acceptance test or it will not be accepted. She said she would have it correct and resent today.
|
INSP-Final Inspection | 6/4/2018 | 6/5/2018 | 6/5/2018 | A | FAIL |
Troy Cobbley
|
|
|
Several of the horn/strobes, as marked on the plans, are overspaced. We did not set off the notification circuit.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
Issue and Print Permit | | | 5/9/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 5/8/2018 | | DONE |
|
|
|
Product data received. Notification calculations, riser and floor plan do not match but are close enough to be functional and have adequate room for expansion. As built corrections required prior to acceptance test.
|
Alarm Plan Check | 5/8/2018 | | 5/8/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/8/2018 | | DONE |
|
|
|
Plans approved with review comments and requirements. As built drawings and documents required prior to acceptance.
|
Permit Ready to Issue | | | 5/8/2018 | | DONE |
|
|
|
All requirements met
|
Plan resubmittals received | | | 5/7/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 5/7/2018 | | 5/7/2018 | | PASS |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 5/7/2018 | | DONE |
|
|
|
Product data has not been provided. Emailed Ken and requested he email it at his earliest convenience.
|
1st review completed | | | 5/1/2018 | | FAIL |
|
|
|
Failed prescreen review. Address and title incorrect. 2 drawings provided. One shows wall mount notificaiton and the other shows ceiling mount.
|
Application received | | | 4/27/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 27 2018 10:34PM
|