Permit Information
Permit NumberFIR18-00360
StatusFinaled
Name WIRETECH LLC
Site Address 2419 W FAIRVIEW AVE
Project NameAdare Manor
Customer Number 
ePlanReviewYes
Description
New Fire Alarm System for New Apartment Structure This work is associated with building permit BLD17-02261.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/27/20199/27/20199/27/2019APASS
DetailsJim Page
Plan mods have been approved and verified, final fire alarm inspection is complete
INSP-Sprinkler Rough-in/Hydro9/27/20199/27/20199/27/2019PCANC
DetailsJim Page
Wrong inspection type for inspection request, this request is cancelled.

.

David Phone #: ###-####
Permit Ready to Issue  9/24/2019 DONE
plan mod approved
DO NOT REISSUE
CHANGE STATUS TO (ISS)  9/24/2019 DONE
plan mod
Fees Due Hold9/13/2019 9/24/2019 DONE
DetailsTiffany Carson-Herker
Plan Mod fees added along with reinspection fee
1st review completed  9/23/2019 PASS
Alarm Plan Check9/23/2019 9/23/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/23/2019 DONE
Plan mod approved. No additional comments.
Plan Modification Accepted  9/18/2019 DONE
INSP-Final Inspection9/12/20199/13/20199/13/2019PPART
DetailsJim Page
Initiating devices in common areas tested. Audio visual notification has been tested. Fire sprinkler initiating devices has been tested. Notification to be added in trash rooms on each floor, will verify before final C of O. Monitoring has been verified.

David Phone #: ###-####
INSP-Final Inspection9/11/20199/12/20199/12/2019PFAIL
DetailsJim Page
Panel shows ground fault trouble, needs to be corrected. FDC bell only rings with level 1 stair 2 riser, no other flow switches are hooked to bell, FDC bell needs to ring during all water flow events.

Trey Phone #: ###-####
INSP-Final Inspection9/6/20199/9/20199/9/2019AFAIL
DetailsJim Page
Audio intelligibility not met in numerous areas. Smoke detector in ADA room on level 1 overspaced, detector is more than 21 foot from corner of room. A/V device in level 1 elevator lobby is overspaced. Notated city approved draiwngs other areas requiring correction. Inspection was stopped on level 2 due to deficiencies noted, all fire sprinkler and initiating devices still and audio visual coverage still need inspected. Monitoring account has been verified, have not checked signals with monitoring as of this entry.

David Phone #: ###-####
INSP-Final Inspection9/5/20199/6/20199/6/2019PFAIL
DetailsJim Page
Walkthrough on level 1 performed, notated city approved drawings with red ink areas requiring correction, inspection stopped on level 1 due to amount of items marked. No sprinkler monitoring devices or initiating devices tested.

David Phone #: ###-####
INSP-Final Inspection8/30/20198/30/20198/30/2019PCANC
DetailsJim Page
Cancelled per conversation with point of contact, will be rescheduled for a later date.

Tre Phone #: ###-####
Plan assigned to (Lee)8/14/2019 8/15/2019 DONE
DetailsLee G Meredith
as built
1st review completed  8/15/2019 PASS
Alarm Plan Check8/15/2019 8/15/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/15/2019 DONE
As built - No fee.
Permit Ready to Issue  8/15/2019 DONE
CHANGE STATUS TO (ISS)  8/15/2019 DONE
per Lee M no fee's for as built
Plan resubmittals received  8/14/2019 DONE
Start as built workflow per Emily at Wiretech
Issue and Print Permit  9/26/2018 DONE
Alarm Plan Check9/24/2018 9/25/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/25/2018 DONE
3rd review approved with review comments.
Permit Ready to Issue  9/25/2018 DONE
Plan resubmittals received  9/24/2018 DONE
Telephone call  9/19/2018 DONE
Conference call with Emily, the designer and Tom & Josh of DC Engineering to discuss failed review comments. All Items discussed. Some items just clarified while others will required design changes, as noted in the review comments.
Plan resubmittals received  9/11/2018 DONE
Alarm Plan Check9/11/2018 9/11/2018 FAIL
DetailsLee G Meredith
See 2nd review comments.
Plan assigned to (Lee)5/10/2018 5/10/2018 DONE
DetailsLee G Meredith
1st review completed  5/10/2018 FAIL
See 1st review comments.
Miscellaneous action  5/10/2018 DONE
Emailed review comments to applicant.
Miscellaneous action  5/8/2018 DONE
Emailed Emily to let her know that we have not received drawings, product data or calculations yet and that these will be required prior to permit review and issuance. She responded to say she had been delayed on the upload but plans on completing it tomorrow.
Application received  5/2/2018 DONE
Application submitted via PDS Online on May 2 2018 9:11AM