Permit Information
Permit NumberFIR18-00395
StatusFinaled
Name AEI SYSTEMS GROUP
Site Address 7609 W OVERLAND RD
Project NameBoise Spectrum Building 'C'-FA
Customer Number 
ePlanReviewYes
Description
Fire Alarm Replacement. This work is Phase 2 of 2 and is not associated with a building permit. Phase 1 is FIR18-00221.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/12/20189/13/20189/19/2018ACANC
DetailsTroy Cobbley
Duplicate inspection

Meet Mike At 7:30 Phone #: ###-#### Inspection requested via web by David Oliver
INSP-Final Inspection9/11/20189/12/20189/19/2018APASS
DetailsTroy Cobbley
Permit finaled 9/13/18

Please meet at 7 am.
Mike Hull and Brian Richard are the Techs on site. Phone #: ###-#### Inspection requested via web by David Oliver
INSP-Alarm Testing9/13/20189/13/20189/13/2018APASS
DetailsLee G Meredith
Manual station that was moved to properlocation tested for function and activation of notification. Testing complete. As built drawings and record of completion received.
DOC - Permit Finaled  9/13/2018 DONE
System passed inspection all required documents provided.
INSP-Final Inspection8/29/20188/31/20188/31/2018ACANC
DetailsTroy Cobbley
I could not make the time as needed by the contractor and the as-builts had not been approved yet.


Please Schedule for as close to 7am as possible to accommodate the tenants.
Thank you.

Dave. ###-####
Phone #: ###-#### Inspection requested via web by David Oliver
Miscellaneous action  8/31/2018 DONE
As built drawings received, reviewed and approved.
INSP-Final Inspection7/20/20187/24/20187/24/2018AFAIL
DetailsTroy Cobbley
No actual testing was performed today. We did however perform a walk through and I noted strobes that are overspaced and acouple that are nmissing. There is a restroom in the northwest corner of the building that needs notification. There is a strobe in a restroom that is not shown on the plans. Several trobes are mounted too low. Several pull stations are mounted too high. As-builts need to be submitted. Plan reviewer may require plan modifications. See the city approved plans for corrections marked in red ink.


Requesting an Early inspection at 7:00 due to Businesses operating hours, please. Phone #: ###-#### Inspection requested via web by David Oliver
1st review completed  5/15/2018 PASS
Alarm Plan Check5/15/2018 5/15/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/15/2018 DONE
Plans approved with review comments and requirements.
Permit Ready to Issue  5/15/2018 DONE
met
Issue and Print Permit  5/15/2018 DONE
Plan assigned to (Lee)5/14/2018 5/14/2018 DONE
DetailsLee G Meredith
Miscellaneous action  5/14/2018 DONE
Emailed Dave to request wall heights arond Legends bar and gaming room areas. Dave responded with a drawing markup that indicated which walls were full height..
Application received  5/11/2018 DONE
Application submitted via PDS Online on May 11 2018 10:29AM