Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR18-00420
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 1005 W MAIN ST
Project NameJohn Alden Building A.G.
Customer Number 
ePlanReviewYes
Description
[John Alden Building Renovation and Addition]
The fire sprinkler scope of work consists of
New fire sprinkler system in existing building (floors 1 thru 5). Modify existing basement fire sprinkler system. The majority of the basement is indicated as future tenant. In addition, the system is being renovated for standpipes and floor control valve. Since this is a change of use the basement fire protection system has to be brought up to current code.

• The underground piping and yard PIV is under permit FIR18-00132.

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
[BLD17-04686]
Permit for core and shell upgrades and the addition of a 5,330 sq. ft. 5th story to the building with work to include, accessible restrooms, minor space reconfigurations and the installation of a new elevator. A separate permit will be required for the interior build out of the tenant spaces. This building is fully fire sprinklered. Separate fire sprinkler and fire alarm permits will be required; as regulated by Boise Fire Department. CDM

Alternative Materials and Methods:

• There are no AMM at this time.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20191/3/20191/3/2019PPASS
DetailsJim Page
Final fire sprinkler for core and shell only complete, TI work is currently in progress under seperate permits.

Phone #: ###-#### Inspection requested via web by jeremiah robison
INSP-Final Inspection12/27/201812/28/201812/28/2018PFAIL
DetailsJim Page
Multiple heads blocked in basement level. Could not test basement flow switch due to sump pump no keeping up with water flow. Exposed combustible material in basement level with no sprinkler protection.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
INSP-Final Inspection12/27/201812/28/201812/27/2018ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Matthew Lewis
INSP-Sprinkler Rough-in/Hydro12/26/201812/26/201812/26/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping on levels 1 and 5 witnessed, no pressure loss observed.

5th floor Hydro Test. Phone #: ###-#### Inspection requested via web by Randy Knutson
INSP-Sprinkler Rough-in/Hydro12/6/201812/10/201812/10/2018PPART
DetailsJim Page
Hydrostatic test for levels 2, 3 and 4 witnessed, no pressure loss observed. Levels 1 and 5 to be completed at a later date.

Leon Taylor is the contact Phone #: ###-#### Inspection requested via web by jeremiah robison
INSP-Sprinkler Rough-in11/5/201811/6/201811/6/2018APASS
DetailsTroy Cobbley
5th floor bathroom and Lobby, see marked approved plans, piping is ok to cover.
INSP-Sprinkler Rough-in10/31/201811/5/201811/5/2018ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact.

Complete Rough-In for 2nd through 5th floor. Call Leon Taylor @ ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in/Hydro10/26/201810/26/201810/26/2018PPART
DetailsJim Page
Hydrostatic test for stairwell standpipes, underground supply and basement system witnessed, no pressure loss observed. Levels 1 through 5 to be completed when heat can be maintained at 40 degrees or above on mentioned floors.

Hydro on the basement feed and Underground coming into the basement.
Hydro on both standpipes.
Call Patrick @ ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Gray
INSP-Supply line flush10/11/201810/16/201810/16/2018ADONE
DetailsJim Page
Underground main line flush complete.

SUEZ will be there at 7am to flush the underground with Steve V. ###-####. Phone #: ###-#### Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in10/10/201810/11/201810/11/2018APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping on basement level complete, cover is not approved at this time.

Basement rough-in. Call Steve V. ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in10/8/201810/10/201810/10/2018APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping on level 1 complete, cover is not approved at this time.

1st Floor rough-in. Call Steve V. ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in9/25/20189/26/20189/26/2018PPART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping on levels 4 and 5 complete, cover is not approved at this time.

Rough-In for 4th and 5th floors. Call Steve Vaughn - ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in9/13/20189/14/20189/14/2018APASS
DetailsAdele J Schaffeld-Griffin
Rough-in for Bathrooms on 1st and 4th floors. approved for cover by Ron Johnson. Phone #: ###-#### >> Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in9/7/20189/10/20189/10/2018APASS
DetailsJim Page
Forrest Inspection results-Rough-in inspection completed for overhead fire sprinkler work at the 2nd and 3rd floor shell and core areas. Approval for ceiling cover at the 2nd
floor restrooms. Contractor to revise over-spacing at four branch lines in the calc area on the 2nd floor as discussed. 3” main re-route appears
acceptable. Two branch lines at the 3rd floor are not yet installed due to stair construction underway.
Rough-In Inspection for 2nd & 3rd floors. Phone #: ###-#### >> Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in8/30/20188/31/20188/31/2018PPASS
DetailsTroy Cobbley
3rd Floor Bathroom Rough-In aboive hard lid only 4 pendent heads, not pressure test done, only ok to cover ceiling for FS. Phone #: ###-#### >> Inspection requested via web by Sheldon Gray
INSP-Sprinkler Rough-in8/23/20188/23/20188/23/2018PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located above the restrooms on level 2 complete, approved for cover.

Call Steve Vaughn. Rough-in for 2nd floor. To cover in the bathrooms. Phone #: ###-#### Inspection requested via web by Sheldon Gray
INSP-Conference7/25/20187/26/20187/26/2018ADONE
DetailsJim Page
Fire conference for standpipe location complete.

for existing standpipe. Please call Randy ###-#### first and if no answer call Steven Vaughn at ###-#### Phone #: ###-#### Inspection requested via web by Matthew Lewis
Permit Ready to Issue  7/17/2018 DONE
Issue and Print Permit  7/17/2018 DONE
Plan resubmittals received  7/16/2018 DONE
Sprinkler Plan Check7/16/2018 7/16/2018 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  7/16/2018 DONE
DetailsTim Frost
Plan resubmittals received  7/12/2018 DONE
Plan assigned to (Tim)7/12/2018 7/12/2018 DONE
DetailsTim Frost
Sprinkler Plan Check7/12/2018 7/12/2018 FAIL
DetailsTim Frost
Changes were not clouded.
Plan resubmittals received  7/6/2018 DONE
Sprinkler Plan Check7/6/2018 7/6/2018 FAIL
DetailsTim Frost
Miscellaneous action  7/6/2018 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Sprinkler Plan Check6/14/2018 6/15/2018 FAIL
DetailsTim Frost
Miscellaneous action  6/15/2018 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Intake Approval  6/14/2018 PASS
Plan assigned to (Tim)6/14/2018 6/14/2018 DONE
DetailsTim Frost
Application received  5/22/2018 DONE
Application submitted via PDS Online on May 22 2018 2:48PM