INSP-Final Inspection | 1/25/2019 | 1/25/2019 | 1/25/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Alarm Testing | 1/24/2019 | 1/25/2019 | 1/25/2019 | A | DONE |
Troy Cobbley
|
|
|
I retested all three elevator lobby detectors for recall, the remaining manual pull stations and all of the flow switches and tamper switches.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Alarm Testing | 1/23/2019 | 1/24/2019 | 1/25/2019 | P | DONE |
Troy Cobbley
|
|
|
Lee witnessed testing of the audio/visuals and smoke dampers.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
INSP-Alarm Testing | 1/2/2019 | 1/2/2019 | 1/2/2019 | P | PART |
Jim Page
|
|
|
Fire alarm testing for level 2 complete except for gym area, gym area to be tested at a later date.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Alarm Testing | 12/28/2018 | 12/28/2018 | 12/28/2018 | P | FAIL |
Jim Page
|
|
|
Provide3 notification in area between offices on southwest corner. Provide correct coverage in restrooms, currently restrooms have shadow issues. Clean up wiring on NAC panels, can't have wires hanging out of panel.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Alarm Testing | 12/27/2018 | 12/28/2018 | 12/28/2018 | A | CANC |
Jim Page
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, December 28, 2018.
|
INSP-Alarm Testing | 12/17/2018 | 12/17/2018 | 12/17/2018 | P | PART |
Troy Cobbley
|
|
|
Phase 1 fire alarm work is complete.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 12/17/2018 | 12/17/2018 | 12/17/2018 | P | PART |
Troy Cobbley
|
|
|
Phase 1 fire alarm work complete. The smoke detectors for elevator return now send alarm not supervisory signals.
Adam Phone #: ###-####
|
INSP-Final Inspection | 12/14/2018 | 12/14/2018 | 12/14/2018 | A | PART |
Jim Page
|
|
|
Fire alarm inspection for level 3 and level 1 lobby complete, fire sprinkker monitoring complete to include standpipe valve supervision. Still need to inspect levels 1 and 2 including pedestrian link.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Alarm Testing | 12/12/2018 | 12/13/2018 | 12/13/2018 | A | FAIL |
Troy Cobbley
|
|
|
The inspection today was just for the third floor. Need horn added in the southwest corner. Need strobe in the Executive Break Room. Need all tampers and flow switches tested that effect the third floor and exit pass. Need elevators tested. Need plan mods showing address changes and different NAC panels being used.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 12/12/2018 | 12/12/2018 | 12/12/2018 | P | PART |
Jim Page
|
|
|
RTU shutdown testing complete, in-duct detectors tested on levels 2 and 3. Still need to test A/V devices and initiating devices for phase 1 TCO requested areas.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Conference | 12/10/2018 | 12/11/2018 | 12/11/2018 | A | DONE |
Jim Page
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price.
On site to review 2nd and 3rd floor strobe placement changes. No problems found. No tests performed.
|
INSP-Alarm Testing | 12/7/2018 | 12/7/2018 | 12/7/2018 | A | FAIL |
Jim Page
|
|
|
Correct overspacing issues throughout level 3. Verify correct candela settings with city approved drawings. Numerous devices have the candele setting incorrect, candela settings need to match city approved drawings. A re-submittal will be required if devices are added to the fire alarm system that is not on the city approved drawings, to include candela adjustment outside of what is shown on city approved drawings. Correct shadowing issues that are throughout level 3. Correct overspacing issues with level 1 lobby A/V devices.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
Plan assigned to (Lee) | 11/8/2018 | | 11/8/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/8/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 11/8/2018 | | 11/8/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/8/2018 | | DONE |
|
|
|
Passed review. Minor changes required, as noted on the drawings. No new review commets.
|
Plan Modification Accepted | | | 11/8/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 11/8/2018 | | 11/8/2018 | | DONE |
Lee G Meredith
|
|
|
Plan modification review passed with noted requirements. No additional review comments provided.
|
PLANS TAKEN FRONT DESK ALARM | | | 11/8/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/8/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/8/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 11/6/2018 | | DONE |
|
|
|
Sheri emailed to request the workflow be opened for a plan modification.
|
Miscellaneous action | | | 10/29/2018 | | DONE |
|
|
|
Charlie Bayne called to discuss changing 3rd floor visible notification for devices approved at 110cd down to 95 cd. He said that the manufacturer does not have 110cd in the same color as other devices throughout. After measuring the spacing, I informed him that 95cd is adequate and he can change device. He will make the changes and provide as built documents that reflect all changes.
|
Miscellaneous action | | | 6/27/2018 | | DONE |
|
|
|
updated calculations received and approved.
|
Alarm Plan Check | 6/25/2018 | | 6/27/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/27/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 6/27/2018 | | DONE |
|
|
|
all requirements met
|
Issue and Print Permit | | | 6/27/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/26/2018 | | DONE |
|
|
|
Calculation sheets have not been updated to reflect the previously required changes. I emailed Sheri and asked her to email these at her earliest convenience. She indicated that she should have it to me by 6/27.
|
Plan resubmittals received | | | 6/25/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 6/25/2018 | | 6/25/2018 | | DONE |
Lee G Meredith
|
|
|
|
Plan assigned to (Lee) | 6/11/2018 | | 6/11/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/11/2018 | | FAIL |
|
|
|
See 1st review comments.
|
Application received | | | 6/6/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 6 2018 2:23PM
|