INSP-Final Inspection | 11/16/2018 | 11/16/2018 | 11/16/2018 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 11/12/2018 | 11/14/2018 | 11/14/2018 | P | PASS |
Lee G Meredith
|
|
|
John Howard - Techinican Phone #: ###-#### >> Inspection requested via web by John Siewert
All notification, 2 waterflows and 2 tampers, 1 manual alarm, 1 smoke and central station monitoring tested. All functioned properly. Record of completion and as built drawings required.
|
Plan assigned to (Lee) | 6/11/2018 | | 6/11/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/11/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 6/11/2018 | | 6/11/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/11/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 6/11/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/11/2018 | | DONE |
|
|
|
|
Application received | | | 6/8/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 8 2018 12:06PM
|