Permit NumberFIR18-00482
StatusFinaled
Name SONITROL PACIFIC
Site Address 7500 W MOSSY CUP ST
Project NameNxedge
Customer Number 
ePlanReviewYes
Description
Provide non-code required notification per owner's request. Provide sprinkler monitoring of a dyke level, as noted on the drawing. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/7/20192/8/20192/8/2019PPASS
DetailsTroy Cobbley
Permit finaled.

Phone #: ###-#### Inspection requested via web by Kyle Burgess
Miscellaneous action  1/31/2019 DONE
As builts received and approved.
INSP-Final Inspection1/28/20191/29/20191/29/2019PFAIL
DetailsTroy Cobbley
Need as-builts/plan mods approved as previously requested. I did a walk through to verify the changes have been implemented. No other testing performed.

Please call 30 min prior so that I can meet onsite Phone #: ###-#### Inspection requested via web by Kyle Burgess
INSP-Final Inspection12/14/201812/17/201812/17/2018PFAIL
DetailsTroy Cobbley
Project is not ready for a final yet. During the initial walk through I found over spaced stobes and one area where new costruction, not shown on the plans, has caused spacing issues with the strobes. Contractor is going to provide as-builts with the modified candellas and addtional strobes required for the new construction. Also I noted to small rooms being used as open office areas that will require notificaiton. No other testing was performed.

Please call before arrival so I can plan to meet at site. Phone #: ###-#### Inspection requested via web by Kyle Burgess
Plan assigned to (Lee)6/15/2018 6/15/2018 DONE
DetailsLee G Meredith
Alarm Plan Check6/15/2018 6/15/2018 PASS
DetailsLee G Meredith
1st review completed  6/15/2018 PASS
PLANS TAKEN FRONT DESK ALARM  6/15/2018 PASS
Permit Ready to Issue  6/15/2018 DONE
All requirements me
Issue and Print Permit  6/15/2018 DONE
Application received  6/14/2018 DONE
Application submitted via PDS Online on Jun 14 2018 3:53PM