Permit Information
Permit NumberFIR18-00486
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 2306 S TRAPPER PL
Project NameHarris Ranch North Lot 24
Customer Number 
ePlanReviewYes
Description
[Harris Ranch North Lot 24 - Ponderosa HN 24-1]
The fire sprinkler scope of work consists of a new single family two level home. The system is designed as a passive purge system. The system utilizes CPVC piping and residential type sprinklers.

[BLD18-01096]
This structure is required to have a NFPA 13D fire sprinkler system per SUB15-00005 *Permit for the construction of a new 3,415 sq. ft., two story (first story 1,748 sq. ft., second story 1,667 sq. ft.) single family dwelling with 4 bedrooms, 3 and a half bathrooms, approximately 369 sq. ft. of covered patio/porch and a 984 sq. ft. attached garage per the approved plans and any notations. W.U.I. Foothills Zone A lot. Class "A" roof required.

Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/5/201811/6/201811/6/2018APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/31/201810/31/201810/31/2018PFAIL
DetailsJim Page
Flow switch did not activate on water flow, paddle for water flow has something resticting full travel. Provide calculation sticker at riser.

Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in8/9/20188/9/20188/9/2018PPASS
DetailsJim Page
Tenting inspectin complete, all plastic sheeting was in place at time of inspection, all overhead fire sprinkler piping approved for cover.

Tenting inspection, call Anthony if there are any concerns. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in8/7/20188/7/20188/7/2018PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping located between conditioned spaces approved for cover, piping located in unconditioned spaces cannot be covered until a tenting inspection is performed.
INSP-Sprinkler Rough-in/Hydro8/6/20188/7/20188/7/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.

Call Anthony to coordinate Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro8/6/20188/6/20188/6/2018PCANC
DetailsJim Page
Inspection request will be rescheuled per conversation with point of contact.

Call Anthony to schedule, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
Issue and Print Permit  7/5/2018 DONE
Plan resubmittals received  6/27/2018 DONE
Sprinkler Plan Check6/27/2018 6/27/2018 PASS
DetailsTim Frost
Plan assigned to (Tim)6/27/2018 6/27/2018 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  6/27/2018 DONE
DetailsTim Frost
Permit Ready to Issue  6/27/2018 DONE
all requirements met
Intake Approval  6/18/2018 PASS
Plan assigned to (Tim)6/18/2018 6/18/2018 DONE
DetailsTim Frost
Sprinkler Plan Check6/18/2018 6/18/2018 FAIL
DetailsTim Frost
1st review completed  6/18/2018 FAIL
DetailsTim Frost
Miscellaneous action  6/18/2018 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Application received  6/15/2018 DONE
Application submitted via PDS Online on Jun 15 2018 4:45PM