INSP-Final Inspection | 1/31/2019 | 2/1/2019 | 2/1/2019 | A | PASS |
Jim Page
|
|
|
Final inspection for clean agent system complete.
On Site Tech Jeremy Egbert - ###-#### Inspection requested via web by Eric Stanley
|
INSP-Sprinkler Rough-in/Hydro | 1/23/2019 | 1/28/2019 | 1/28/2019 | A | FAIL |
Jim Page
|
|
|
Smoke detectors in server room are to close to HVAC registers, need a minimum of 36 inshes from air flow edge to smoke detectors. Verify allowed clearance around nozzles as well as distance from wall.
.
Jeremy Phone #: ###-####
|
Plan Modification Accepted | | | 10/9/2018 | | DONE |
Tim Frost
|
|
|
|
Plan assigned to (Tim) | 10/9/2018 | | 10/9/2018 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 10/9/2018 | | 10/9/2018 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/9/2018 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 10/9/2018 | | DONE |
|
|
|
Plan Mod Approved
Do Not ReIssue
|
Issue and Print Permit | | | 10/9/2018 | | DONE |
|
|
|
|
Intake Approval | | | 10/5/2018 | | FAIL |
Tim Frost
|
|
|
Dwg in wrong orientation.
|
Plan assigned to (Tim) | 10/5/2018 | | 10/5/2018 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/1/2018 | | 8/1/2018 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/1/2018 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 8/1/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/1/2018 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/19/2018 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 7/19/2018 | | 7/19/2018 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/19/2018 | | 7/19/2018 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 6/25/2018 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 6/25/2018 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Sprinkler Plan Check | 6/22/2018 | | 6/25/2018 | | FAIL |
Tim Frost
|
|
|
|
Intake Approval | | | 6/22/2018 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 6/22/2018 | | 6/22/2018 | | DONE |
Tim Frost
|
|
|
|
Intake Approval | | | 6/22/2018 | | FAIL |
|
|
|
|
Plan assigned to (Tim) | 6/22/2018 | | 6/22/2018 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 6/20/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 20 2018 1:30PM
|