Permit Information
Permit NumberFIR18-00503
StatusFinaled
Name PROTEX
Site Address 1300 S BIRD ST
Project NameIdaho Humane Society
Customer Number 
ePlanReviewYes
Description
Add code-compliant fire alarm control panel for the purposes of manual pull, smoke detection and annunciation. This work is associated with building permit BLD17-02871. Plan Mod 10-28-19. Change notification power supplies to resolve syncronization issues.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/30/201910/30/201910/30/2019PPASS
DetailsTroy Cobbley
Permit finaled

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)10/29/2019 10/30/2019 DONE
DetailsLee G Meredith
as built
1st review completed  10/30/2019 DONE
Alarm Plan Check10/30/2019 10/30/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/30/2019 DONE
As built - No fee.
CHANGE STATUS TO (ISS)  10/30/2019 DONE
2nd plan mod as built no fee per Lee
INSP-Final Inspection10/28/201910/29/201910/29/2019PFAIL
DetailsTroy Cobbley
Changes verified. Plan mods are needed showing the missing detector at first floor elevator lobby and the three NAC panels that are paired with the three other NAC panels. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  10/29/2019 DONE
Morgan with Protex asked for the eplan work flow to be opened for as builts.
Plan assigned to (Lee)10/25/2019 10/28/2019 DONE
DetailsLee G Meredith
Plan modification to change notification power supplies to resolve syncronization issues.
1st review completed  10/28/2019 PASS
Alarm Plan Check10/28/2019 10/28/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/28/2019 DONE
Plan mod passed. Fee is $65.00 for one hour minimum.
Permit Ready to Issue  10/28/2019 DONE
DO NOT ISSUE plan mod
CHANGE STATUS TO (ISS)  10/28/2019 DONE
PLAN MOD
INSP-Final Inspection10/24/201910/25/201910/25/2019PCANC
DetailsJim Page
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
Plan resubmittals received  10/25/2019 DONE
Morgan from Protex called to start an as built workflow
INSP-Final Inspection10/24/201910/25/201910/24/2019ACANC
DetailsTroy Cobbley
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
Plan assigned to (Lee)10/16/2019 10/23/2019 DONE
DetailsLee G Meredith
Intake Approval  10/23/2019 PASS
1st review completed  10/23/2019 PASS
Alarm Plan Check10/23/2019 10/23/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/23/2019 DONE
As built - No fee
Permit Ready to Issue  10/23/2019 DONE
CHANGE STATUS TO (ISS)  10/23/2019 DONE
Plan Modification Accepted  10/16/2019 DONE
as built as per morgan with protex
INSP-Alarm Testing10/9/201910/10/201910/10/2019PDONE
DetailsTroy Cobbley
Tested the remaining smoke detectors and elevator recall. Per Lee the volume of the horns has been verified by a third party and is ok. Items need prior to a final sign off are the sync issue with the horns and the previously noted changes need to be applied. Plan mods are needed showing all of the changes.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Alarm Testing10/9/201910/9/201910/9/2019PDONE
DetailsTroy Cobbley
Todays inspection we tested the smoke detectors in the first floor central area and the north wing. All tested ok. We set off the notification for the entire building and I noted that the visual devices have two patterns which is ok but the audible devices do not sync which is not ok as per NFPA 72.
Also the smoke detectors are reporting correctly.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)10/7/2019 10/8/2019 DONE
DetailsLee G Meredith
as built
1st review completed  10/8/2019 PASS
Alarm Plan Check10/8/2019 10/8/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/8/2019 DONE
As built - No fee
Permit Ready to Issue  10/8/2019 DONE
as built approved
CHANGE STATUS TO (ISS)  10/8/2019 DONE
Plan resubmittals received  10/7/2019 DONE
start a as built workflow per Morgan at Protex
INSP-Alarm Testing10/4/201910/4/201910/4/2019PFAIL
DetailsTroy Cobbley
The smoke detectors are not reporting to the facp. Inspection stopped. The receiver troubles have been cleared.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Alarm Testing10/1/201910/2/201910/2/2019PDONE
DetailsTroy Cobbley
Today we finished the building walk through for the notification appliances. See the city approved plans for locations of deficiencies. Approx. 30 items. The fire alarm panel currently has dial out issues and does not appear to be reporting signals. Plans need to be resubmitted showing the candella changes and that many of the smoke detectors have not been installed. No smoke detectors were tested due to the communication troubles on the fire alarm panel.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection9/30/201910/1/201910/1/2019AFAIL
DetailsTroy Cobbley
For todays inspection I was able to check spaqcing of the south wing and center section first floor. Several devices are overspaced and many more had the candellas set incorrectly. Plans do not match the install such as horns shown but horn/strobes installed (the horn/strobes are required) Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)9/25/2019 9/26/2019 DONE
DetailsLee G Meredith
As BUILT
1st review completed  9/26/2019 PASS
Alarm Plan Check9/26/2019 9/26/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/26/2019 DONE
As built - No Fee.
Permit Ready to Issue  9/26/2019 DONE
as built
CHANGE STATUS TO (ISS)  9/26/2019 DONE
as built
Plan Modification Accepted  9/25/2019 DONE
as built
INSP-Final Inspection9/13/20199/16/20199/16/2019AFAIL
DetailsTroy Cobbley
Audibility levels tested. Most areas exceeded the maximum allowable volume of 110 dB and peaked between 112 and 116. All areas need to be reduced to below 110 dB. jonathan Phone #: ###-####.
INSP-Alarm Testing7/11/20197/12/20197/12/2019ADONE
DetailsTroy Cobbley
Todays inspection we verified phone lines, panel, duct detector/hvac unit shutdown, flow switches and tamper switches.
Plan modifications are needed showing all of the changes. Strobes are over spaced and need to be relocated or the candella adjusted. Smoke detectors are too close to diffusers. Strobes are missing in on location on the second floor as marked on the plans.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Conference2/28/20193/4/20193/4/2019ADONE
DetailsTroy Cobbley
I went over smoke detector spacing with the electrical and fire alarm contractor. I deferred elevator recall requirement to state inspector.

Contact Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Alarm Plan Check2/11/2019 2/11/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/11/2019 DONE
Passed with review comments and drawing notation.
Permit Ready to Issue  2/11/2019 DONE
met
Issue and Print Permit  2/11/2019 DONE
Plan resubmittals received  2/7/2019 DONE
Most changes do not appear to have been made. Emailed Morgan to verify correct drawings were uploaded.
Alarm Plan Check1/24/2019 1/24/2019 FAIL
DetailsLee G Meredith
Numerous errors on floor plans for detection and notification. Returned to Morgan for corrections.
Plan resubmittals received  1/23/2019 DONE
Plan resubmittals received  11/19/2018 DONE
Alarm Plan Check11/19/2018 11/19/2018 FAIL
DetailsLee G Meredith
Detector spacing does not meet the requirements of NFPA 72. Some notification is not adequate.
Plan resubmittals received  11/15/2018 DONE
Returned to Morgan. Replacement drawings did not have proper file names for corrected drawings.
Miscellaneous action  7/26/2018 DONE
Notified Morgan that visible and audible notification is inadequate throughout and will be returned for corrections. Also noted that detector spacing has not been reviewed at this time but that it will be required to meet 900 sq. ft. spacing in all required areas. Design is being returned for corrections.
Alarm Plan Check7/25/2018 7/26/2018 FAIL
DetailsLee G Meredith
Plan resubmittals received  7/25/2018 DONE
Plan assigned to (Lee)7/5/2018 7/6/2018 DONE
DetailsLee G Meredith
1st review completed  7/6/2018 FAIL
Candela not shown on floor plan. Riser indicates 15cd candela for all devices, regardless of room size. Returned for correction - compliance with NFPA 72 18.5.5.4.1.
Application received  6/25/2018 DONE
Application submitted via PDS Online on Jun 25 2018 12:22PM