INSP-Final Inspection | 7/23/2018 | 7/24/2018 | 7/24/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
John Phone #: ###-####
|
INSP-Alarm Testing | 7/20/2018 | 7/23/2018 | 7/23/2018 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
John Phone #: ###-####
|
Alarm Plan Check | 7/17/2018 | | 7/18/2018 | | DONE |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/18/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 7/18/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/18/2018 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 7/16/2018 | | 7/17/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/17/2018 | | FAIL |
|
|
|
Failed pre-screen review. Parts storage area requires audible storage to meet a minimum of 15dbA above ambient sound levels in every occupied area. Strobes are requried in all common areas per NFPA 72 but only if this area is non-seperated ber building code section 508. John called to discuss the issue and I explained it this way.
|
Plan resubmittals received | | | 7/17/2018 | | DONE |
|
|
|
|
Application received | | | 7/16/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 16 2018 9:34PM
|