Permit Information
Permit NumberFIR18-00559
StatusFinaled
Name TKG PROTECTION SYSTEMS
Site Address 11196 W FAIRVIEW AVE
Project NameLarry Miller Subaru Pump Add
Customer Number 
ePlanReviewYes
Description
Connect new fire pump, flow switch and tamper switches to the existing Fire Alarm System. This work is associated with building permit BLD17-02975.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/23/20187/24/20187/24/2018APASS
DetailsTroy Cobbley
Permit finaled

John Phone #: ###-####
INSP-Alarm Testing7/20/20187/23/20187/23/2018PPASS
DetailsTroy Cobbley
Permit finaled

John Phone #: ###-####
Alarm Plan Check7/17/2018 7/18/2018 DONE
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/18/2018 DONE
Plans approved with review comments.
Permit Ready to Issue  7/18/2018 DONE
Issue and Print Permit  7/18/2018 DONE
Plan assigned to (Lee)7/16/2018 7/17/2018 DONE
DetailsLee G Meredith
1st review completed  7/17/2018 FAIL
Failed pre-screen review. Parts storage area requires audible storage to meet a minimum of 15dbA above ambient sound levels in every occupied area. Strobes are requried in all common areas per NFPA 72 but only if this area is non-seperated ber building code section 508. John called to discuss the issue and I explained it this way.
Plan resubmittals received  7/17/2018 DONE
Application received  7/16/2018 DONE
Application submitted via PDS Online on Jul 16 2018 9:34PM