Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00566
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 12311 W BRADDOCK DR
Project NameSpalding STEM Academy
Customer Number 
ePlanReviewYes
Description
Spalding STEM Academy - Existing Building Control Panel/Voice Evacuation Panel is being installed. This work is associated with building permit BLD18-01191. Plan modification 10-2-18. Change wall mount notification to ceiling mount. Add 57 more smoke detectors for door release. Plan modification 10-16-18. Modify design for door holder release. Some areas will use corridor full coverage instead of added detection at the corridor side of the door.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/27/201812/28/201812/28/2018APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/18/201812/18/201812/18/2018PCANC
DetailsTroy Cobbley
Not ready per Nathan and will be rescheduled.

Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Conference12/6/201812/6/201812/6/2018PDONE
DetailsTroy Cobbley
Went over strobe spacing with the electrian. I noted several strobes that will need to be relocated or increased candella. I'm questioning the placement and function of smoke detector 81 in the Gymnasium.
INSP-Alarm Testing11/21/201811/21/201811/21/2018PDONE
DetailsTroy Cobbley
The low air switch has been replaced and tested. The strobe in Room 9 has been replaced and tested. The fire alarm system in the existing school is complete except for some of the doors do not swing shut when the door mag released. To final project the doors will need to be addressed, as-builts and the new portion of the school will need to be completed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Alarm Testing11/19/201811/20/201811/20/2018ADONE
DetailsTroy Cobbley
Today we tested the interconnection of the existing fire alarm devices with the new panel. All devices on the existing risers functioned except the "low air" pressure switch on the System #1 did not function. It will need to be replaced asap as discussed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
Plan Modification Accepted  11/20/2018 DONE
DetailsLee G Meredith
Alarm Plan Check11/19/2018 11/20/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/20/2018 DONE
Plan modification approved. No additional review comments.
Permit Ready to Issue  11/20/2018 DONE
Plan Mod Approved
CHANGE STATUS TO (ISS)  11/20/2018 DONE
INSP-Alarm Testing11/19/201811/19/201811/19/2018ADONE
DetailsTroy Cobbley
We tested the smoke detectors and notification devices today. All functioned except for the strobe in the back of Room 9. I also noted several doors that did not swing shut when the door mags released.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Alarm Testing11/16/201811/16/201811/16/2018PDONE
DetailsTroy Cobbley
For todays inspection I only verified device locations. I noted smoke detectors needing centered on the door on the classroom side. Per a later phone call from Lee these detectors are ok to be deleted as long as the distance from the header to the ceiling does not exceed 24". I also noted many strobes that are overspaced in nearly every classroom and atleast one in the main corridor. I noted that the communication means being used is not what is shown on the approved plans. As-builts will be required but possibly for plan mods.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
Miscellaneous action  11/16/2018 DONE
As built drawings showing classroom detectors have been removed. Measurments to be verified by the inspector. Candela has been increased where strobes were moved. All appears acceptable, subject to inspection.
Miscellaneous action  10/16/2018 DONE
Sheri Carlson requested the work flow be re-opened so a plan modification can be submitted.
Miscellaneous action  10/16/2018 DONE
Nathan emailed to indicate the originally planned panel is no longer in production and will be replaced with a Silent Knight 6820XL-EVS. I informed him that as built drawings and calculations will be required at the completion of the project that indicates the changes.
Plan Modification Accepted  10/16/2018 DONE
1st review completed  10/16/2018 PASS
Alarm Plan Check10/16/2018 10/16/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/16/2018 DONE
Plan modification approved with revised review comments.
Permit Ready to Issue  10/16/2018 DONE
CHANGE STATUS TO (ISS)  10/16/2018 DONE
(F) Reprint permit  10/16/2018 DONE
Plan Modification Accepted  10/2/2018 DONE
Alarm Plan Check10/2/2018 10/2/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/2/2018 DONE
Plan mod approved with review comments.
Permit Ready to Issue  10/2/2018 DONE
plan mod do not re issue
CHANGE STATUS TO (ISS)  10/2/2018 DONE
(F) Reprint permit  10/2/2018 DONE
Miscellaneous action  10/1/2018 DONE
Sheri requested the work flow be opened for a plan modification that includes adding detection for fire smoke damper control and moving notification from the walls to the ceiling.
Plan resubmittals received  8/3/2018 DONE
Alarm Plan Check8/3/2018 8/3/2018 DONE
DetailsLee G Meredith
Resubmittal plans approved as noted.
PLANS TAKEN FRONT DESK ALARM  8/3/2018 DONE
Plans approved with review comments and inspectors drawing notes.
Permit Ready to Issue  8/3/2018 DONE
Issue and Print Permit  8/3/2018 DONE
Miscellaneous action  7/24/2018 DONE
Drawings failed review and were returned to Sheri with changemarks on floor plans. Drawings are to be corrected and resubmitted.
Plan assigned to (Lee)7/23/2018 7/23/2018 DONE
DetailsLee G Meredith
Miscellaneous action  7/23/2018 DONE
Some classroom walls appear to be blocking the strobe. I emailed charlie to have him verify the height of the walls to determine actual requirements.
7/24/18 Charlie responded to say the walls are full height and that they will need to add strobes. Plans to be returned for corrections.
Application received  7/18/2018 DONE
Application submitted via PDS Online on Jul 18 2018 9:26AM