Permit NumberFIR18-00569
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 13255 W MCMILLAN RD
Project NamePioneer Elementary
Customer Number 
ePlanReviewYes
Description
Adding initiation, duct detection and voice notification to an existing fire alarm system in an existing building with new classrooms and a new gymnasium. This work is associated with building permit BLD18-01190.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/1/20191/2/20191/2/2019APASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection12/27/201812/28/201812/28/2018AFAIL
DetailsTroy Cobbley

Need as-builts/plan mods for all of the candella changes, need to discuss Entry way notification with plan review and add if required, need weather proof backbox in Dishwashing area on the speaker strobe, need to verify phone lines, need to verify equipment and batteries, need to verify dedicated circuit, need to verify function of notification.


Ken Phone #: ###-####
Telephone call  12/27/2018  
Ken stated that 3 sets of doors required the addition of mag door holders and associated detection. Wanted to know if a resubmittal was required. I told him if the mag holders released on a loss of power, calcs. would not be affected so they could be provided on as built drawings. Also, he is adding one wall mounted detector in the gym for door hoder release. Installation is to be on the wall within 5 feet of the door per NFPA 72 17.4.8.
INSP-Alarm Testing12/17/201812/18/201812/18/2018ADONE
DetailsTroy Cobbley
The testing of the fire smoke dampers performed today. One is no-functional and will need to be re-tested.

Buck-partial Phone #: ###-####
INSP-Alarm Testing12/13/201812/14/201812/14/2018ADONE
DetailsTroy Cobbley
Today we tested the second duct smoke detector that failed to work yesterday. Today it functioned correctly.

inspecting in -ducts in Pioneer gym Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Alarm Testing12/12/201812/13/201812/13/2018APART
DetailsTroy Cobbley
Only the four fire smoke dampers and the east side duct detector were tested today in the Gym. The west side hvac unit did not function.

Phone #: ###-#### Inspection requested via web by Ken Webster
Plan resubmittals received  7/30/2018 DONE
Alarm Plan Check7/27/2018 7/30/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/30/2018 DONE
Plans approved with review comments.
Permit Ready to Issue  7/30/2018 DONE
Issue and Print Permit  7/30/2018 DONE
Plan assigned to (Lee)7/20/2018 7/20/2018 DONE
DetailsLee G Meredith
1st review completed  7/20/2018 FAIL
Failed pre-screen review. Duct detection monitoring and control not shown for 4 new roof top units. Discussed this with Ken and he said he would add this information to drawings and calculations.
Application received  7/18/2018 DONE
Application submitted via PDS Online on Jul 18 2018 10:57AM