INSP-Final Inspection | 1/1/2019 | 1/2/2019 | 1/2/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 | A | FAIL |
Troy Cobbley
|
|
|
Need as-builts/plan mods for all of the candella changes, need to discuss Entry way notification with plan review and add if required, need weather proof backbox in Dishwashing area on the speaker strobe, need to verify phone lines, need to verify equipment and batteries, need to verify dedicated circuit, need to verify function of notification.
Ken Phone #: ###-####
|
Telephone call | | | 12/27/2018 | | |
|
|
|
Ken stated that 3 sets of doors required the addition of mag door holders and associated detection. Wanted to know if a resubmittal was required. I told him if the mag holders released on a loss of power, calcs. would not be affected so they could be provided on as built drawings. Also, he is adding one wall mounted detector in the gym for door hoder release. Installation is to be on the wall within 5 feet of the door per NFPA 72 17.4.8.
|
INSP-Alarm Testing | 12/17/2018 | 12/18/2018 | 12/18/2018 | A | DONE |
Troy Cobbley
|
|
|
The testing of the fire smoke dampers performed today. One is no-functional and will need to be re-tested.
Buck-partial Phone #: ###-####
|
INSP-Alarm Testing | 12/13/2018 | 12/14/2018 | 12/14/2018 | A | DONE |
Troy Cobbley
|
|
|
Today we tested the second duct smoke detector that failed to work yesterday. Today it functioned correctly.
inspecting in -ducts in Pioneer gym Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Alarm Testing | 12/12/2018 | 12/13/2018 | 12/13/2018 | A | PART |
Troy Cobbley
|
|
|
Only the four fire smoke dampers and the east side duct detector were tested today in the Gym. The west side hvac unit did not function.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
Plan resubmittals received | | | 7/30/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 7/27/2018 | | 7/30/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/30/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 7/30/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/30/2018 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 7/20/2018 | | 7/20/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/20/2018 | | FAIL |
|
|
|
Failed pre-screen review. Duct detection monitoring and control not shown for 4 new roof top units. Discussed this with Ken and he said he would add this information to drawings and calculations.
|
Application received | | | 7/18/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 18 2018 10:57AM
|