INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 11/4/2018 | 11/5/2018 | 11/5/2018 | A | CANC |
Troy Cobbley
|
|
|
We received the ROC but as-builts have not been provided. Ken will have finished tonight and submitted tomorrow.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 11/1/2018 | 11/1/2018 | 11/1/2018 | P | FAIL |
Troy Cobbley
|
|
|
The duct smoke detectors keep giving a invalid responce signal and a calibration signal and the remote LED's do not latch upon alarm.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 10/29/2018 | 10/30/2018 | 10/30/2018 | A | FAIL |
Troy Cobbley
|
|
|
The duct smoke detectors failed to operate/shutdown the hvac units.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 10/28/2018 | 10/29/2018 | 10/29/2018 | A | FAIL |
Troy Cobbley
|
|
|
The lifts on site could not be used. Also as-builts have not been provided to plan review yet
Ken Webster ###-#### Buck Tom ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 10/25/2018 | 10/26/2018 | 10/26/2018 | A | PART |
Troy Cobbley
|
|
|
A temporary for life safety for this permiti is being given with the fire code and building code officials permission until the map is provided, duct detector function tested, strobe coverage corrected, as-builts, battery calcs which include the new dialer.
Phone #: ###-#### Inspection requested via web by Ken Webster
|
Issue and Print Permit | | | 7/24/2018 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 7/19/2018 | | 7/20/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/20/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 7/19/2018 | | 7/20/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/20/2018 | | DONE |
|
|
|
Plans approved with review comments and drawing notes.
|
Permit Ready to Issue | | | 7/20/2018 | | DONE |
|
|
|
|
Application received | | | 7/18/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 18 2018 11:05AM
|