Permit Information
Permit NumberFIR18-00639
StatusFinaled
Name ALL VALLEY FIRE INSPECTIONS AND SER
Site Address 2180 W BENT BOW CT
Project NameMitchell Residence
Customer Number 
ePlanReviewYes
Description
[Mitchell Residence - Eyrie Canyon 36-1]
The fire sprinkler scope of work consists of a new single family one level home. The system is designed as a dedicated fire protection system. The system utilizes CPVC piping and residential type sprinklers.

[BLD18-01107]
**This structure is required to have a NFPA 13D fire sprinkler system. ** W.U.I. Foothills Class "A" Roof Required. Permit for the construction of a new 2,728 sq. ft., one story single family dwelling with 3 bedrooms, 2.5 bathrooms, approximately 108 sq. ft. of covered patio/porch and a 1,620 sq. ft. attached garage per the approved plans and any notations. Prescriptive Energy Compliance. A-1 zoning and setbacks per planning. ***RDP***

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/26/201811/27/201811/27/2018APASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection complete.

Johnathon Phone #: ###-####
INSP-Sprinkler Rough-in11/19/201811/20/201811/20/2018AFAIL
DetailsJim Page
One head in main entry and one head in corridor between bedrooms are less than 4 inches off of wall, heads need to be relocated to be 4 inches or more from walls. Fire bell needs to be relocated to be seen from the address side of street. Need to perform hydrostatic test at city static pressure before final inspection can be completed.

John-overhead Phone #: ###-####
INSP-Sprinkler Rough-in9/4/20189/4/20189/4/2018PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.

John Phone #: ###-####
Intake Approval  8/16/2018 PASS
Plan assigned to (Tim)8/16/2018 8/16/2018 DONE
DetailsTim Frost
Sprinkler Plan Check8/16/2018 8/16/2018 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  8/16/2018 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  8/16/2018 DONE
DetailsTim Frost
Permit Ready to Issue  8/16/2018 DONE
Issue and Print Permit  8/16/2018 DONE
Application received  8/14/2018 DONE
Application submitted via PDS Online on Aug 14 2018 12:02PM