Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00644
StatusFinaled
Name PROTEX
Site Address 3722 W ANDERSON ST
Project NameTaft Elementary Update
Customer Number 
ePlanReviewYes
Description
Upgrade existing fire alarm control panel to a voice system. This work is associated with building permit BLD18-00945.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/29/20193/29/20193/29/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire alarm inspection complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)3/28/2019 3/29/2019 DONE
DetailsLee G Meredith
1st review completed  3/29/2019 PASS
Alarm Plan Check3/29/2019 3/29/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/29/2019 DONE
As built passed. Actual conditions to be verified by inspector.
Permit Ready to Issue  3/29/2019  
as built, no fee per Lee
Issue and Print Permit  3/29/2019 DONE
INSP-Final Inspection3/27/20193/28/20193/28/2019AFAIL
DetailsJim Page
Fire panel that was installed does not match what was submitted. Communicator showing trouble at time of inspection. In-duct detectors report to panel as a trouble with no RTU shutdown on both HVAC units. Provide a different type of notification appliance in horn location, horns do not sync with speaker strobes as well as overpowering the sound of the surrounding speaker strobes. Signals were not verified at time of inspection.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  3/28/2019 DONE
as built per morgan with protex
INSP-Final Inspection3/22/20193/25/20193/25/2019PFAIL
DetailsJim Page
Two speaker strobes in gym area are blocked by ducting. Need to test in-ducts for HVAC unit shutdown. Wire hanging out of communicator to fire panel.



Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/14/20193/14/20193/14/2019PPART
DetailsJim Page
Fire alarm audible device now meets the required NFPA 72 sound level requirements in the new kitchen area..

Final is for Kitchen Only. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/12/20193/13/20193/13/2019PFAIL
DetailsJim Page
Audible level was not met in kitchen area.

This final is only for the kitchen portion. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Miscellaneous action  3/12/2019 DONE
Rob called to say the school district decided to remove interface between buildings but the seperate GSM will be kept. I told him to provide as builts when tiime for sign off.
Miscellaneous action  3/11/2019 DONE
Notification changed back to horns only so speakers and strobes removed from kitchen. Inspector to verify that audibility levels in the kitchen are adequate.
Miscellaneous action  2/28/2019 DONE
Received product data for a GSM communicator and updated riser drawing.
Plan resubmittals received  8/29/2018 DONE
Alarm Plan Check8/29/2018 8/29/2018 PASS
DetailsLee G Meredith
Approved with drawing notes and requirements.
PLANS TAKEN FRONT DESK ALARM  8/29/2018 DONE
Plans approve with review comments and requirements.
Permit Ready to Issue  8/29/2018 DONE
all requirement met
Issue and Print Permit  8/29/2018 DONE
Plan assigned to (Lee)8/27/2018 8/27/2018 DONE
DetailsLee G Meredith
1st review completed  8/27/2018 DONE
Failed pre-screen review. Returned to Morgan so a scale graph could be added.
Application received  8/15/2018 DONE
Application submitted via PDS Online on Aug 15 2018 12:54PM