INSP-Final Inspection | 5/20/2019 | 5/20/2019 | 5/20/2019 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
please have this aft 3:00 pm if possible call joe 30 min prior to inspect ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
Plan resubmittals received | | | 5/16/2019 | | DONE |
|
|
|
Per Kristin at Johnson Controls - start as built workflow
|
INSP-Final Inspection | 5/9/2019 | 5/10/2019 | 5/10/2019 | A | PART |
Mark Scharfen
|
|
|
Tested system. TCO of 10 days granted to verify 6 corrections. Approved by Ron Johnson
ada room strobes do not turn off until reset. sounders in rooms 101, 107, 118 sound steady (bad base).
2 smokes in beam pockets to be lowered to bottom of beam (greater than .1 less than .4)
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
CHANGE STATUS TO (ISS) | | | 5/10/2019 | | DONE |
|
|
|
permit finaled by mistake, only temp CO approved on 5/10/19
|
INSP-Final Inspection | 5/7/2019 | 5/8/2019 | 5/8/2019 | A | FAIL |
Mark Scharfen
|
|
|
Checked candella and smoke placment. Tested sprinkler interconnect and cell monitoring. While testing C wing found several problems:
Sounder bases in room will not resound alarms.
Room 309 bedroom strobe failed.
no ac labels on fire or nac panels.
Cell Dact needs to be added to fire alarm drawing and submitted as an as-build.
access control doors do not drop on fire alarm.
Did not verify horn strobe functionality in rest of building.
Still need to test majority of smoke detectors, CO detectors, access control interface, majority of notification devices.
Please call when in route. We are finalling sprinkler and FA at the same time. Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
|
Issue and Print Permit | | | 4/30/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 4/24/2019 | | 4/29/2019 | | DONE |
Lee G Meredith
|
|
|
|
Plan resubmittals received | | | 4/29/2019 | | DONE |
|
|
|
|
1st review completed | | | 4/29/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 4/29/2019 | | 4/29/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/29/2019 | | DONE |
|
|
|
Passed as noted. No additional comments.
|
Permit Ready to Issue | | | 4/29/2019 | | DONE |
|
|
|
Plan mod
|
Miscellaneous action | | | 4/25/2019 | | DONE |
|
|
|
Emailed Kristin to see what changes were made. Uploaded drawings do not appear to have any. Found that uploaded drawings were markups for the drafter to make. Returned for corrections.
|
Plan Modification Accepted | | | 4/24/2019 | | DONE |
|
|
|
plan mod DO NOT REISSUE per Kristin Nolan
|
CHANGE STATUS TO (ISS) | | | 11/26/2018 | | DONE |
|
|
|
|
(F) Reprint permit | | | 11/26/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/19/2018 | | DONE |
|
|
|
do no re issue-plan mod
|
Plan resubmittals received | | | 11/16/2018 | | DONE |
|
|
|
|
Alarm Plan Check | 11/16/2018 | | 11/16/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/16/2018 | | DONE |
|
|
|
Plan mod passed with review comments.
|
Plan Modification Accepted | | | 11/9/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 11/9/2018 | | DONE |
|
|
|
File names are incorrect. Returned to Shane to have the file names corrected to exactly match previously submitted files.
|
Plan Modification Accepted | | | 10/31/2018 | | DONE |
|
|
|
Plan modification is required by the state to add visible notification in several areas.
|
Alarm Plan Check | 10/31/2018 | | 10/31/2018 | | FAIL |
Lee G Meredith
|
|
|
|
CHANGE STATUS TO (REV) | | | 10/31/2018 | | DONE |
|
|
|
Changed status to REV for plan mod review.
|
Miscellaneous action | | | 10/30/2018 | | DONE |
|
|
|
Shane requested the workflow be reopened to resubmit plan modifications for additional visible notificaiton.
|
Plan assigned to (Lee) | 9/4/2018 | | 9/5/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/5/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 9/4/2018 | | 9/5/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/5/2018 | | DONE |
|
|
|
Plans approved with review comments and required changes noted on drawings.
|
Permit Ready to Issue | | | 9/5/2018 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/5/2018 | | DONE |
|
|
|
|
Application received | | | 9/4/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 4 2018 11:22AM
|