Permit Information
Permit NumberFIR18-00690
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 4455 E WARM SPRINGS AVE
Project NameAspen Valley Senior Living
Customer Number 
ePlanReviewYes
Description
Provide and install a new automatic and manual fire alarm system with sprinkler monitoring, in room system detectors with sounder bases, corridor detection and full notification in common areas. This work is associated with building permit BLD18-00494.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/20/20195/20/20195/20/2019PPASS
DetailsJim Page
Final fire alarm inspection complete.

please have this aft 3:00 pm if possible call joe 30 min prior to inspect ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
Plan resubmittals received  5/16/2019 DONE
Per Kristin at Johnson Controls - start as built workflow
INSP-Final Inspection5/9/20195/10/20195/10/2019APART
DetailsMark Scharfen
Tested system. TCO of 10 days granted to verify 6 corrections. Approved by Ron Johnson

ada room strobes do not turn off until reset.
sounders in rooms 101, 107, 118 sound steady (bad base).

2 smokes in beam pockets to be lowered to bottom of beam (greater than .1 less than .4)



Phone #: ###-#### Inspection requested via web by Kristin Dolan
CHANGE STATUS TO (ISS)  5/10/2019 DONE
permit finaled by mistake, only temp CO approved on 5/10/19
INSP-Final Inspection5/7/20195/8/20195/8/2019AFAIL
DetailsMark Scharfen
Checked candella and smoke placment. Tested sprinkler interconnect and cell monitoring. While testing C wing found several problems:

Sounder bases in room will not resound alarms.
Room 309 bedroom strobe failed.
no ac labels on fire or nac panels.
Cell Dact needs to be added to fire alarm drawing and submitted as an as-build.
access control doors do not drop on fire alarm.

Did not verify horn strobe functionality in rest of building.

Still need to test majority of smoke detectors, CO detectors, access control interface, majority of notification devices.

Please call when in route. We are finalling sprinkler and FA at the same time. Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
Issue and Print Permit  4/30/2019 DONE
Plan assigned to (Lee)4/24/2019 4/29/2019 DONE
DetailsLee G Meredith
Plan resubmittals received  4/29/2019 DONE
1st review completed  4/29/2019 PASS
Alarm Plan Check4/29/2019 4/29/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/29/2019 DONE
Passed as noted. No additional comments.
Permit Ready to Issue  4/29/2019 DONE
Plan mod
Miscellaneous action  4/25/2019 DONE
Emailed Kristin to see what changes were made. Uploaded drawings do not appear to have any. Found that uploaded drawings were markups for the drafter to make. Returned for corrections.
Plan Modification Accepted  4/24/2019 DONE
plan mod DO NOT REISSUE per Kristin Nolan
CHANGE STATUS TO (ISS)  11/26/2018 DONE
(F) Reprint permit  11/26/2018 DONE
Permit Ready to Issue  11/19/2018 DONE
do no re issue-plan mod
Plan resubmittals received  11/16/2018 DONE
Alarm Plan Check11/16/2018 11/16/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/16/2018 DONE
Plan mod passed with review comments.
Plan Modification Accepted  11/9/2018 DONE
Miscellaneous action  11/9/2018 DONE
File names are incorrect. Returned to Shane to have the file names corrected to exactly match previously submitted files.
Plan Modification Accepted  10/31/2018 DONE
Plan modification is required by the state to add visible notification in several areas.
Alarm Plan Check10/31/2018 10/31/2018 FAIL
DetailsLee G Meredith
CHANGE STATUS TO (REV)  10/31/2018 DONE
Changed status to REV for plan mod review.
Miscellaneous action  10/30/2018 DONE
Shane requested the workflow be reopened to resubmit plan modifications for additional visible notificaiton.
Plan assigned to (Lee)9/4/2018 9/5/2018 DONE
DetailsLee G Meredith
1st review completed  9/5/2018 PASS
Alarm Plan Check9/4/2018 9/5/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/5/2018 DONE
Plans approved with review comments and required changes noted on drawings.
Permit Ready to Issue  9/5/2018 DONE
Issue and Print Permit  9/5/2018 DONE
Application received  9/4/2018 DONE
Application submitted via PDS Online on Sep 4 2018 11:22AM