Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR18-00732
StatusFinaled
Name MOUNTAIN ALARM
Site Address 8601 W EMERALD ST
Project NameECP 8601
Customer Number 
ePlanReviewYes
Description
Replace existing Silent Knight 5207 FACP (obsolete) with new Silent Knight 5208 FACP. There does not appear to be an associated building permit.**Plan Mod** Add annunciators, pulls and flows in a manner that seperates signals from the individual buildings.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit Ready to Issue  6/13/2019 DONE
As built approved
CHANGE STATUS TO (ISS)  6/13/2019 DONE
DOC - Permit Finaled  6/13/2019 DONE
Final acceptance test passed 6-6-19 and as builts approved 6-13-19.
Plan assigned to (Lee)6/6/2019 6/12/2019 DONE
DetailsLee G Meredith
as built
1st review completed  6/12/2019 PASS
Alarm Plan Check6/12/2019 6/12/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/12/2019 DONE
As built - No Fee
INSP-Final Inspection6/3/20196/4/20196/6/2019PFAIL
DetailsTroy Cobbley
Permit will be ok for final when as-builts are approved.

Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
Plan resubmittals received  6/6/2019 DONE
Rose Peterson from Mountain Alarm requested an as built open, per Lee.
1st review completed  6/3/2019 PASS
Alarm Plan Check6/3/2019 6/3/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/3/2019 DONE
Passed. No additional review comments. As built drawings and product datat required prior to acceptance.
Permit Ready to Issue  6/3/2019 DONE
plan mod
CHANGE STATUS TO (ISS)  6/3/2019 DONE
Plan assigned to (Scharfen)5/17/2019 5/28/2019 DONE
DetailsLee G Meredith
Miscellaneous action  5/28/2019 DONE
Emailed Rose to see if circuit isolation was included in the design for all circuits between buildings.
Plan Modification Accepted  5/17/2019 DONE
8601 red line changes and added pulse stations
INSP-Final Inspection3/26/20193/28/20193/28/2019AFAIL
DetailsTroy Cobbley
Resubmit plans that show entire scope of work that includes all devices in all buildings. Devices shall annunciate by the building address. Installation shall meet NFPA 72. Provide updated battery and notification circuit calculations. Separate remote annunciators maybe required for each building. Lightning protection may be required for circuits connecting each building. All buildings may require riser room pull stations. The horns on the exterior of the building may not be required.

Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection1/24/20191/30/20191/30/2019ACANC
DetailsTroy Cobbley
Cancel per Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection12/28/20181/4/20191/2/2019ACANC
DetailsTroy Cobbley
Ray McQueen, inspecting technician Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
INSP-Final Inspection10/4/201810/9/201810/8/2018ACANC
DetailsTroy Cobbley
Ray McQueen, inspecting technician, building access is open Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
Issue and Print Permit  9/27/2018 DONE
Plan assigned to (Lee)9/20/2018 9/24/2018 DONE
DetailsLee G Meredith
1st review completed  9/24/2018 PASS
Alarm Plan Check9/20/2018 9/24/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/24/2018 DONE
Plans approved with review comments and requirements.
Permit Ready to Issue  9/24/2018 DONE
met
Application received  9/20/2018 DONE
Application submitted via PDS Online on Sep 20 2018 1:29PM